USING THE TEC-EYE

ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
TEC-EYE HAND-HELD DIAGNOSTIC
TOOL
The microprocessor control used in this wall mount
air conditioning system allows for complete control
and monitoring through the use of the provided TEC-
EYE hand-held monitor. This comprehensive service
tool utilizes the latest in state-of-the-art technology
including a large, easy-to-read backlit LCD graphic
display.
The menu driven interface provides users the ability
to scroll through three menu levels: Info, Control and
Service. The menus permit the user to easily view,
control and configure the unit.
The controller is completely programmed at the factory;
therefore, most applications will require no field set-up.
However, the default setpoints and their ranges are
easily viewed and adjusted from the TEC-EYE display.
The program and operating parameters are permanently
stored on FLASH-MEMORY in case of power failure.
The controller is designed to manage temperature
levels to a user-defined setpoint via control output
signals to the wall mount air conditioning system.
The TEC-EYE connects to the wall-mount unit control
board via an RJ11 modular phone connector as shown
in Figure 2.9.
Manual 2100-620A
Page
54 of 107
FIGURE 2.8
TEC-EYE Display
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
The TEC-EYE hand-held diagnostic tool should be
stored somewhere inside the shelter, preferably close
to the Bard-Link
integrated magnets on the back of the tool, so it can be
attached to the front, sides, bottom, or top of the PLC
control box.
TEC-EYE Connection to Unit Control
UP KEY
ENTER KEY
DOWN KEY
PLC controller. The TEC-EYE has