2. Installing Remote Indoor Temperature Sensor(s)
A single remote indoor temperature sensor is included with the controller. This sensor must be installed for proper
operation. Use the included 35' shielded cable to mount the temperature sensor in a location least likely to be
affected by open doors, rack-mounted fans, radiant heat sources, etc. Locating the sensor between both return grilles
is often the best location, but every installation is unique. Location height should be approximately 48" above the
floor. The sensor should be installed on a 4" by 4" junction box to allow for control wire conduit (see Figure 1.14).
For proper operation, the remote indoor temperature sensors must be configured properly with the controller. If only
the single remote indoor temperature sensor supplied with the controller is installed, the configuration setting is
2.
Connect the other end of the 35' shielded cable to either of
the sensor terminals. These connections are also not polarity
sensitive.
Sensor is best mounted on a junction box, and it is
recommended that the cable be in conduit.
Manual 2100-620A
Page
22 of 107
FIGURE 1.14
Remote Indoor Temperature Sensor Installation
1.
Connect wires from provided 35' shielded cable to terminals
#11 and #12. The connection is not polarity-sensitive.