APPENDIX 1: LC-SERIES CONTROLLER ARCHITECTURE

CAUTION: The Bard DC-FCU System has been pre-programmed with what is widely considered to be the best
settings for efficiency and operation. Any changes to internal programming through the LC-Series Controller or the
TEC-EYE not covered within this manual may cause the systems to operate improperly, cause internal damage to
the HVAC units, cause the shelter to overheat, or other very serious consequences. Although complete controller
programming architecture for both the LC-Controller and TEC-EYE has been provided, going outside the boundaries
of what has been covered in this manual not recommended.
Screen
Status Screen
(Use UP/DOWN arrow keys to scroll)
Space Temp
Setpoint
Unit 1 Blower
Unit 1 Damper
Unit 1 Compressor
Unit 2 Blower
Unit 2 Damper
Unit 2 Compressor
Status
U1
U2
Unit 1 / Unit 2 SAT
Unit 1 / Unit 2 RAT
Unit 1 / Unit 2 OAT
Unit 1 / Unit 2 OAH
DEW
Last Hour Averages
Inside Temp Avg
Outside Temp Avg
Outside Hum Avg
OA Dewpoint Avg
Last Hour Tracking
Free Cool U1/U2 Run
Free Cool U1/U2 Start
Compressor 1 U1/U2 Run
Compressor 1 U1/U2 Start
Compressor 2 U1/U2 Run
Compressor 2 U1/U2 Start
Manual 2100-620A
Page
92 of 107
Menu Item
(Current Temp)
°F Setpoint
Off/On
%
C1/nothing
Off/On
%
C2/nothing
Unit On
Online
Online
°F
°F
°F
%H
°F
°F
%H
°F
Minutes
#
Minutes
#
Minutes
#
Value
Displays current data
Displays status of blower
Displays percentage of current opening
Displays status of compressor
Displays status of blower
Displays percentage of current opening
Displays status of compressor
LC-Series controller is currently
enabled ("Off by Keypad" if disabled in
controller)
Verification of communication with Unit
1
Verification of communication with Unit
2
Supply air temperature (discharge air
temperature)
Return air temperature
Outdoor air temperature
Outdoor air humidity
Averages from last hour of operation
Statistics from last 60 min of operation
Running minutes of damper activation
Damper initiations
Compressor run time (single stage units
or 1st stage compressor of 2-stage
units)
Compressor initiations (single stage
units or 1st stage compressor of 2-stage
units)
2nd stage compressor run time
2nd stage initiations
Description