Manual 2100-620A - Bard D36A2P/BLD.10304 Installation And Service Instructions Manual

Replacement parts manual dc free cooling unit system two (2) d-series dual-tec™ wall-mounted package one (1) bard-linktm plc lead/lag controller controller models lc1000-100/bld.10293, lc1500-100/bld.10291
Table of Contents

Advertisement

APPENDIX 1: LC-SERIES CONTROLLER ARCHITECTURE (CONT.)
Screen
Manual Position
Value
Digital Inputs
Smoke Manual DI 1
Manual Position
D1 Status
Hydrogen Manual DI 2
Manual Position
D2 Status
Generator Run DI 3
Manual Position
D3 Status
Relay Outputs
Smoke Manual Relay 1
Manual Position
Relay 1 Status
High Temp Relay 4
Manual Position
Relay 4 Status
Low Temp Relay 5
Manual Position
Relay 5 Status
HVAC 1 Fail Relay 6
Manual Position
Relay 6 Status

Manual 2100-620A

Page
96 of 107
Menu Item
0
(Temp + Value)
Off
Open/Closed
Open
Off
Open/Closed
Open
Off
Closed
Open
Off
On/Off
On
Off
On/Off
On
Off
On/Off
On
Off
On/Off
On
Value
Degrees of change in sensor for manual
control
Current temperature plus the value in
manual position
"On" to allow artificial manipulation of
smoke alarminput
Change to "Closed" to artifically create
smoke alarm input
Current status of smoke alarm input
(open means no input)
"On" to allow artificial manipulation of
hydrogen alarm input
Change to "Closed" to artifically create
hydrogen alarm input
Current status of hydrogen alarm input
(open means no input)
"On" to allow artificial manipulation of
generator run input
Change to "Closed" to artifically create
generator run input
Current status of generator run input
(open means no input)
"On" to allow artificial manipulation of
smoke alarm relay action
Change to "Off" to artificially force
smoke alarm relay
Current status of smoke alarm relay (on
means no relay action)
"On" to allow artificial manipulation of
high temp alarm relay action
Change to "Off" to artificially force high
temp alarm relay
Current status of high temp alarm relay
(on means no relay action)
"On" to allow artificial manipulation of
low temp alarm relay action
Change to "Off" to artificially force low
temp alarm relay
Current status of low temp alarm relay
(on means no relay action)
"On" to allow artificial manipulation of
HVAC 1 fail relay action
Change to "Off" to artificially force
HVAC 1 fail relay action)
Current status of HVAC 1 fail relay (on
means no relay action)
Description