APPENDIX 2: TEC-EYE ARCHITECTURE (CONT.)
Screen
D2 Status
High Pressure DI 3
Manual Position
D3 Status
Low Pressure DI 4
Manual Position
D3 Status
Blower Status DI 5
Manual Position
D3 Status
Damper Switch Status DI 6
Manual Position
D3 Status
Relay Outputs
Cooling Stg 1 Manual Relay 2 Off
Manual Position
Relay 2 Status
Cooling Stg 2 Manual Relay 3 Off
Manual Position
Relay 3 Status
Heating Manual Relay 4
Manual Position
Relay 4 Status
Blower Manual Relay 4

Manual 2100-620A

Page
104 of 107
Menu Item
Closed
Off
Open/Closed
Closed
Off
Open/Closed
Closed
Off
Open/Closed
Closed
Off
Open/Closed
Closed
On/Off
Off
On/Off
Off
Off
On/Off
Off
Off
Value
Current status of filter switch input
(closed means no input)
"On" to allow artificial manipulation of
high pressure switch input
Change to "Closed" to artifically create
high pressure input
Current status of high pressure input
(open means no input)
"On" to allow artificial manipulation of
low pressure switch input
Change to "Closed" to artifically create
low pressure input
Current status of low pressure input
(open means no input)
"On" to allow artificial manipulation of
blower status input
Change to "Closed" to artifically create
blower status input
Current status of blower status input
(open means no input)
"On" to allow artificial manipulation of
damper switch status input
Change to "Closed" to artificially create
damper switch status input
Current status of damper switch status
input (open means no input)
"On" to allow artificial manipulation of
cooling stage 1 relay action
Change to "On" to artificially force
cooling stage 1 relay
Current status of cooling stage 1 relay
(off means no relay action)
"On" to allow artificial manipulation of
cooling stage 2 relay action
Change to "On" to artificially force
cooling stage 2 relay
Current status of cooling stage 2 relay
(off means no relay action)
"On" to allow artificial manipulation of
heating relay action
Change to "On" to artificially force
heating relay
Current status of heating relay (off
means no relay action)
"On" to allow artificial manipulation of
blower relay action
Description