Installing Remote Indoor Temperature/Humidity Sensor(S); Sensor Installation - Bard Fusion-Tec Installation Instructions Manual

Hide thumbs Also See for Fusion-Tec:
Table of Contents

Advertisement

Installing Remote Indoor Temperature/Humidity Sensor(s)

One remote indoor temperature/humidity sensor and 35' of 18 gauge 5-conductor shielded cable is included with the
controller. This sensor must be installed for proper operation. Mount the temperature/humidity sensor in a location
least likely to be affected by open doors, rack-mounted fans, radiant heat sources, etc. Location height should be
approximately 60" above the floor. The sensor should be installed on a 2" x 4" junction box to allow for control wire
conduit (see Figure 19). Use shielded cable to connect to controller.
1.
Connect wires from the 18 gauge shielded cable to terminals #24, #25, #18, #19 and #30.
TB#
Sensor
24
NTC OUT Indoor Temperature 1
25
NTC OUT Ground
18
OUT H
Indoor Humidity 1 Signal: 0-1 VDC
19
M (G)
Indoor Humidity 1 Common
30
+ (G)
Indoor Humidity 1 Power
4 5
6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
2.
Connect the other end of the shielded cable to the sensor
terminals. Be sure wires are connected to proper terminals
as shown in table above. Sensor jumpers need to be
positioned for 0-1 V. With sensor oriented as shown in
image to right, move both jumpers to left position (DP1 and
DP2 set to OFF).
This applies to all temperature/humidity sensors connected
to the LV controller.
Sensor is best mounted on a junction box, and it is
recommended that the cable be in conduit.
Manual 2100-674A
Page
22 of 41
FIGURE 19
Remote Indoor Temperature/Humidity Sensor Installation
Description
LV1000 Terminal Block
DP1
DP2
Wire
Mark
B6
GND
B2
GND
+VDC
Jumper