Fault Codes - Viessmann Vitodens 333-F Service Instructions Manual

Compact gas fired condensing boiler 3.8 to 26 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333-F:
Table of Contents

Advertisement

Fault display
(cont.)
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults are saved
and may be scanned.
The faults are ordered by date, thus
the most recent fault is fault number 1.

Fault codes

Fault
Const.
weath.-
code
comp.
on the
display
0F
X
X
10
X
18
X
20
X
X
Press the following keys:
1. G + d simultaneously for
2. a/b
3. Note
All saved fault codes can be
deleted with e.
4. d
System char-
Cause
acteristics
Control mode
Service
Regulates as
Outside tem-
if the outside
perature
temperature
sensor
was 0 °C
shorted out
Regulates as
Outside tem-
if the outside
perature
temperature
sensor lead
was 0 °C
broken
Regulates
System flow
without flow
temperature
temperature
sensor
sensor (low
shorted out
loss header)
Troubleshooting
approx. 2 s.
for individual fault
codes.
Scanning is completed.
Measures
Service the equip-
ment. After the
service, set cod-
ing address
"24:0".
Check the outside
temperature sen-
sor (see page 87)
Check the outside
temperature sen-
sor (see page 87)
Check the low
loss header sen-
sor (see page 89)
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents