Fault display
(cont.)
4. d
Scanning is completed.
Fault codes
Fault
Const.
code on
the dis-
play
0F
X
10
18
20
28
30
X
38
X
weath.-
System char-
comp.
acteristics
X
Control mode
X
Controls as if
the outside
temperature
were 0 °C
X
Controls as if
the outside
temperature
were 0 °C
X
Regulates with-
out flow tem-
perature sen-
sor (low loss
header)
X
Regulates with-
out flow tem-
perature sen-
sor (low loss
header)
X
Burner blocked Short circuit,
X
Burner blocked Boiler water
Troubleshooting
Cause
Measures
Maintenance
Service the equip-
ment. After the
service, set coding
address "24:0"
Short circuit,
Check the outside
outside tem-
temperature sen-
perature sen-
sor (see
sor
page 83)
Break, out-
Check the outside
side tempera-
temperature sen-
ture sensor
sor (see
page 83)
Short circuit -
Check the low loss
system flow
header sensor (see
temperature
page 85)
sensor
Break, sys-
Check the low loss
tem flow tem-
header sensor (see
perature sen-
page 85)
sor
Check the boiler
boiler water
water temperature
temperature
sensor (see
sensor
page 85)
Check the boiler
temperature
water temperature
sensor lead
sensor (see
broken
page 85)
73