Code 2
(cont.)
Coding in the delivered condition
F7:25
In "Standby mode", the
internal circulation
pump is permanently
ON (only for constant
temperature control
units)
F8:-5
Temperature limit for
terminating the reduced
mode -5 ºC, see exam-
ple on page 112.
Observe the setting of
coding address "A3".
(only for weather-com-
pensated control units)
F9:-14
Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 112.
(only for weather-com-
pensated control units)
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature, by
20 %. See example on
page 113 (only for
weather-compensated
control units).
Possible change
F7:0
In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
In "Standby mode", the
to
internal circulation pump
F7:24
in operating mode will be
started for 10 min respec-
tively 1 to 24 times per
day.
F8:+10
Temperature limit adjus-
to
table from
F8:-60
+10 to -60 °C
F8:-61
Function disabled
F9:+10
Temperature limit for rais-
to
ing the set room tempera-
F9:-60
ture to the value selected
for standard mode adjus-
table from
+10 to -60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50 %
FA:50
Coding