Viessmann Vitodens 333-F Service Instructions Manual page 47

Compact gas fired condensing boiler 3.8 to 26 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333-F:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Max. boiler water temp.
06:...
Maximum limit of the
boiler water tempera-
ture, defaulted in °C by
the boiler coding card
Venting/filling
2F:0
Programs disabled
Subscriber no.
77:1
LON subscriber number
(only for weather-com-
pensated control units)
Summer econ. A1/M2
A5:5
With heating circuit
pump logic function
(only for weather-com-
pensated control units)
Min. flow temp. A1/M2
C5:20
Electronic minimum
flow temperature limit
20 °C (only for weather-
compensated control
units)
Max. flow temp. A1/M2
C6:74
Electronic maximum
flow temperature limit
74 °C (only for weather-
compensated control
units)
Slope A1/M2
d3:14
Heating curve slope =
1.4 (only for weather-
compensated control
units)
Possible change
06:20
Maximum limit of the boil-
to
er water temperature
06:127
within the ranges de-
faulted by the boiler
2F:1
Venting program enabled
2F:2
Fill program enabled
77:2
LON subscriber number,
to
adjustable from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only once.
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 10 to 127 °C (limited
C5:127
by the boiler coding card)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by the boiler coding card)
d3:2
Heating curve slope ad-
to
justable from 0.2 to 3.5
d3:35
(see page 38)
Coding
47