Viessmann Vitodens 333-F Service Instructions Manual page 57

Compact gas fired condensing boiler 3.8 to 26 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333-F:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
97:0
With LON communica-
tion module: The out-
side temperature of the
sensor connected to the
control unit is utilised
internally (only for
weather-compensated
control units)
98:1
Viessmann system
number (in conjunction
with monitoring several
systems via
Vitocom 300)
9b:0
No minimum set boiler
water temperature for
external demand
9C:20
Monitoring LON sub-
scribers.
If a subscriber fails to
respond, the values de-
faulted inside the con-
trol unit will be used
after 20 min. Only then
will a fault message be
issued. (only for weath-
er-compensated control
units)
9F:8
Differential temperature
8 K; only in conjunction
with the mixer circuit
(only for weather-com-
pensated control units)
Heating circuit A1/M2
A0:0
Without remote control
(only for weather-com-
pensated control units)
Possible change
97:1
The control unit receives
the outside temperature
97:2
The control unit sends
the outside temperature
to the Vitotronic 200-H
98:1
System number adjusta-
to
ble from 1 to 5
98:5
9b:1
Minimum set boiler water
to
temperature adjustable
9b:127
from 1 to 127 °C (limited
by the boiler-specific
parameters)
9C:0
No monitoring
9C:5
The time is adjustable
to
from 5 to 60 min
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
Coding
57