Viessmann Vitodens 333-F Service Instructions Manual page 82

Compact gas fired condensing boiler 3.8 to 26 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333-F:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault
Const.
weath.-
code
comp.
on the
display
C7
X
X
Cd
X
X
CE
X
X
CF
X
dA
X
db
X
82
System char-
Cause
acteristics
Control mode,
Communica-
tion fault –
max. pump
speed
external vari-
able speed
heating cir-
cuit pump,
heating
circuit A1
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Control mode
Communica-
tion fault –
ext. exten-
sion
Control mode
Communica-
tion fault,
LON com-
munication
module
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
shorted out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
with mixer
M2 shorted
out
Measures
Check setting of
coding address
"E5"
Check connec-
tions, Vitocom 100
and coding ad-
dress "95"
Check connec-
tions and coding
address "2E"
Replace the LON
communication
module
Check the room
temperature sen-
sor, heating cir-
cuit A1
Check the room
temperature sen-
sor, heating cir-
cuit with mixer M2