Viessmann Vitodens 333-F Service Instructions Manual page 83

Compact gas fired condensing boiler 3.8 to 26 kw natural gas and lpg version
Hide thumbs Also See for Vitodens 333-F:
Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
weath.-
code
comp.
on the
display
dd
X
dE
X
E4
X
X
E5
X
X
E6
X
X
E8
X
X
E9
X
X
System char-
Cause
acteristics
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
lead broken
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
with mixer
M2 lead bro-
ken
Burner
Fault, supply
blocked
voltage 24 V
Fault – flame
Burner
blocked
amplifier
Burner
System
blocked
pressure too
low
Burner in a
The ionisa-
fault state
tion current
lies outside
the permissi-
ble range
Burner in a
The ionisa-
fault state
tion current
lies outside
the permissi-
ble range
during cali-
bration
Troubleshooting
Measures
Check the room
temperature sen-
sor, heating cir-
cuit A1 and the
remote control
DIP switch set-
tings (see
page 114)
Check the room
temperature sen-
sor, heating cir-
cuit with mixer M2
and the remote
control DIP switch
settings (see
page 114)
Replace the con-
trol unit.
Replace the con-
trol unit.
Top up with water.
Check the ionisa-
tion electrode and
cable.
Press "E
RESET".
Check the ionisa-
tion electrode and
cable.
Check the flue
gas system for
tightness.
Press "E
RESET".
83