Scope Of Delivery; Logano G515 - Delivery As A Pre-Assembled Block; Logano G515 - Delivery In Loose Sections; Transporting The Boiler - Buderus Logano G515 Installation And Service Instructions Manual

Low-temperature oil/gas boiler buderus logano g515
Hide thumbs Also See for Logano G515:
Table of Contents

Advertisement

4

Scope of delivery

Logano G515
Boiler capacity
Maximum permissible supply
3)
temperature
Maximum permissible operating
pressure
Table 4
1) Weight with packaging approx. 6–8% higher.
2) The details relate to the upper and lower rated output range.
3) Safety limit (high limit safety cut-out). Maximum possible supply temperature = safety limit (STB) – 32 °F (–18 K).
Example: Safety limit (STB): = 212 °F (100 °C), max. possible supply temperature = 212–32 = 180 °F (100–18 = 82 °C).
4
Scope of delivery
The Logano G515 can be delivered either as a pre-assembled block or in
loose sections.
▶ Check that the packaging is undamaged on delivery.
▶ Check that the delivery is complete.
4.1
Logano G515 – Delivery as a pre-assembled block
Component
Boiler block with burner door and draft
diverter
Assembly components (longitudinal rails
and supply pipe)
Jacket Pack A, B, C (according to boiler
rating)
Thermal insulation
Table 5
4.2
Logano G515 – Delivery in loose sections
Component
Front and rear section as well as burner
door
Intermediate sections – (depending on
boiler size)
Fittings
Exhaust manifold
Tie rods
Assembly components (longitudinal rails
and supply pipe)
Jacket Pack A, B, C (according to boiler
rating)
Thermal insulation
Table 6
10
Unit
240
°F
( °C)
PSI
(bar)
Qty
Packaging
1
Pallet
1
Box
1 – 3
Cartons
1
PU bag
Qty
Packaging
1
Pallet
1 – 2
Pallet
1
Box
1
Box
1
bundle
1
Box
1 – 3
Cartons
1
PU bag
295
350
248
(120)
87
(6)
5

Transporting the boiler

Use suitable equipment to transport the individual boiler sections
(delivery as loose sections) and other individual parts.
WARNING: Risk of injury from improperly secured
boiler sections.
▶ Use only suitable means of transportation when
handling the boiler sections, e.g. a heavy duty hand
truck.
▶ Secure the individual boiler sections to prevent them
from sliding off during transport.
NOTICE: Risk of system damage from impacts.
▶ The standard delivery of the Logano G515 oil/gas-
fired boiler contains components that are sensitive
to shock.
▶ During handling protect all electronic and other
components against impact.
▶ Please observe the transport instructions on the
packaging.
NOTICE: Risk of system damage from contamination.
▶ If you intend to keep the boiler in storage once it has
been assembled, observe the following:
▶ Protect the boiler connections against
contamination by sealing them off or covering them.
Dispose of packaging in an environmentally responsible
manner.
400
455
Logano G515 – 6 720 647 208 (2014/09)
510