Inspection And Maintenance Logs - Buderus Logano G515 Installation And Service Instructions Manual

Low-temperature oil/gas boiler buderus logano g515
Hide thumbs Also See for Logano G515:
Table of Contents

Advertisement

13
System inspection and maintenance
13.7

Inspection and maintenance logs

The inspection and maintenance logs provide an overview of the
required inspection and maintenance work.
Inspection work
1.
Check general condition of heating system
2.
Visual inspection and function check of the heating system
3.
Check fuel and water-carrying components of the system for:
• Leaks during operation
• Visible signs of corrosion
• Signs of aging
4.
Check the combustion chamber and heating surfaces for contamination.
Shut down the heating system first.
5.
Check the burner ( burner documentation)
6.
Check the flue gas and venting system for proper operation and safety
(see  burner documentation)
7.
Check the operating pressure and inlet pressure of the diaphragm
expansion vessel for heating systems
8.
Check the function of indirect-fired heater and rod ( tank
documentation)
Check the control panel setting (see  control panel documentation)
9.
10.
Record the final checks of the inspection work, incl. measurements and
test results
Confirm professional inspection
If during inspection work conditions are identified that require additional service and maintenance, perform this work on an as-needed
basis. If make-up water is added, the quality of this water must correspond to the specifications in the enclosed operating manual.
42
▶ Initial and date the inspection operations completed.
The inspection and maintenance logs can also be used as templates.
Page
Date:____________
 39
 41
Company stamp/signature
Date:____________
Company stamp/signature
Logano G515 – 6 720 647 208 (2014/09)