Calculating The System Current Draw; 1: Overview; 2: How To Use Table 5.3 On Page 138 To Calculate System Current Draw - Fire-Lite MS-9600 User Manual

Fire alarm control panel
Hide thumbs Also See for MS-9600:
Table of Contents

Advertisement

Calculating the System Current Draw

5.3 Calculating the System Current Draw
To convert...
Milliamperes (mA) to
amperes (A)
Microamperes (
amperes (A)
MS-9600 PN 51335:E 7/9/03
5.3.1 Overview
The control panel must be able to power all internal and external devices continuously
during the non-fire alarm condition. To calculate the non-fire alarm load on the system
power supply when primary power is applied, use Calculation Column 1 in Table 5.3 on
page 138. The control panel must support a larger load current during a fire alarm con-
dition. To calculate the fire alarm load on the power supply, use Calculation Column 2
in Table 5.3 on page 138. The secondary power source (batteries) must be able to
power the system during a primary power loss. To calculate the non-fire alarm load on
the secondary power source, use Calculation Column 3 in Table 5.3 on page 138.
When calculating current draw and the battery size, note the following:
• 'Primary' refers to the main power source for the control panel
• 'Secondary' refers to the control panel's backup batteries
• All currents are given in amperes (A). Table 5.2 shows how to convert milliam-
peres and microamperes to full amperes.
Table 5.2 Converting to Full Amperes
µ
A) to
µ
A x 0.000001
5.3.2 How to Use Table 5.3 on page 138 to Calculate System
Current Draw
Use Table 5.3 on page 138 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Fire-Lite Device
Compatibility Document for compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 139
Following are the types of current that can be entered into Table 5.3 on page 138:
Calculation Column 1 - The primary supply current load that the control
panel must support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control
panel must support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a
non-fire alarm condition during a loss of AC power.
Multiply
mA x 0.001
3 mA x 0.001 = 0.003A
µ
300
Power Supply Calculations
Example
A x 0.000001 = 0.0003 A
137

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9600e

Table of Contents