Fire-Lite MS-9600 Supplement

Smoke detector capacity detector sensitivity & synchronized strobes positive alarm sequence & printer supervision
Hide thumbs Also See for MS-9600:

Advertisement

This Supplement has been created to inform installers about the new Signal Line Circuit (SLC) capacity
of 159 detectors and 159 modules per SLC loop; and
Introduce two new FACP software features which (1) provide a synchronized strobe programming
option, (2) allow the control panel to monitor and printout the sensitivity and drift compensation for
each addressable smoke detector connected to the system; as well as to
Provide information concerning 'Positive Alarm Sequence' and 'Printer Supervision'.
I. Synchronized Strobes
NAC Option for Synchronization
Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on
and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to conform
with a variety of regulations as well as to avoid random activation which could cause a hazardous condition. The FACP can be
programmed to operate with a variety of manufacturer's devices.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and
the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed. The visual
devices (strobes, etc.) will continue to operate.
Program Selection for Synchronized Strobes
1. Press the Enter or Mode key to display the following LCD readout:
2. Press 2 to display the following:
3. Enter the Master level password (default is 00000) to display the following:
4. Press down arrow key once to display the following:
Supplement to MS-9600 Manual, Rev A
Detector Sensitivity & Synchronized Strobes
Positive Alarm Sequence & Printer Supervision
1=READ@STATUS
2=PROGRAMMING
PROGRAMMING
ENTER PASSWORD
*****
@@@@@PROGRAMMING
1=POINT@PROGRAM
2=ZONE@SETUP
3=LOOP@SETUP
@@@@PROGRAMMING
1=SYSTEM@SETUP
2=AUTOPROGRAM
3=VERIFY@LOOP
Doc. # 51583 Rev. B 05/07/01 ECN 01-131
Smoke Detector Capacity
Document 51583 Rev B 05/07/01 ECN 01-131
Page 1 of 5

Advertisement

loading

Summary of Contents for Fire-Lite MS-9600

  • Page 1 Supplement to MS-9600 Manual, Rev A Smoke Detector Capacity Detector Sensitivity & Synchronized Strobes Positive Alarm Sequence & Printer Supervision Document 51583 Rev B 05/07/01 ECN 01-131 This Supplement has been created to inform installers about the new Signal Line Circuit (SLC) capacity of 159 detectors and 159 modules per SLC loop;...
  • Page 2 11. Press 1 to program the NAC as a synchronized strobe circuit. 5. Press 1 to display the following: The display will return to the following: @@@@SYSTEM@SETUP @@@@NAC@# 1=TROUBLE@REM@@OFF 1=ENABLED@@@YES 2=BANNER 2=TYPE 3=TIME-DATE 3=SILENCEABLE 12. Press the down arrow key three time to display the following: 6.
  • Page 3 II. Addressable Smoke Detector Sensitivity Software Enhancement The FACP software has been enhanced to include a feature which allows the control panel to monitor the sensitivity of each addressable smoke detector in the system. This eliminates the need for a service person to physically connect a sensitivity test meter to each device in the field.
  • Page 4 A printout, similar to the following example, will be generated if an optional printer is connected to the FACP. DEVICE# DEVICE TYPE %DRIFT COMP. CHAMBER TIME/DATE 1D001 SMOKE (PHOTO) 1478 12:01AM 01-08-2001 1D002 SMOKE (PHOTO) 1362 12:01AM 01-08-2001 1D003 SMOKE (PHOTO) 1452 12:01AM 01-08-2001 1D004...
  • Page 5 The following information is provided as a clarification to the 9600 Fire Alarm Control Panel manual. 1. PAS (Positive Alarm Sequence) programming feature. Refer to the 9600 manual page 47 and page 114 for information on this option. The PAS option is not available in the initial release of the 9600 software. Do not attempt to use this feature since it is not yet functional in this product.