Appendix D: Wire Requirements - Fire-Lite MS-9600 User Manual

Fire alarm control panel
Hide thumbs Also See for MS-9600:
Table of Contents

Advertisement

Wire Requirements
APPENDIX D
T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total
resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot
exceed 10,000 feet (3,000 m).
Connecting external system accessories to the MS-9600 main circuits must be carefully considered
to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run
length for each MS-9600 circuit. Reference the chart below to specify wire requirements and
limitations for each MS-9600 circuit.
Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of
encountering problems can be greatly reduced by exclusively employing electronic sounders (such
as MA/SS-24D) instead of more electronically noisy notification appliances such as
electromechanical bells or horns.
CIRCUIT CONNECTIONS
Circuit Type
Circuit Function
SLC loop
Connects to
(power-limited)
Addressable
Devices
ACS/TERM
Connects to
(EIA-485)
annunciator
(power-limited)
modules and
UDACT-F
EIA-232
connects to
(power-limited)
remote printer
and PC computer
MMF-300 and
Initiating Device
MMF-301
Circuit
(power-limited)
MMF-302
Initiating Device
(power-limited)
Circuit
CMF-300
Notification
(power-limited)
Appliance
Circuit
24 VDC
Connects to
filtered
4-wire smoke
resettable
detectors
(power-limited)
24 VDC
Connects to
nonresettable
control modules,
(power-limited)
annunciators and
accessories
CHG-120F
Remote
secondary power
source
Table Footnote
1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
156
Wire Requirements
Table D.1 MS-9600 Wire Specifications
Recommended
Wire Type and Limitations
Max. Distance
Feet (meters)
Twisted, shielded pair, 40
10,000 (3,000 m)
ohms maximum per length
8,000 (2,400 m)
of Style 6 and 7 loops. 40
4,875 (1,450 m)
ohms per branch maximum
3,225 (980 m)
1
for Style 4 loops
Untwisted, unshielded pair
3,000 (900 m)
Twisted, shielded pair with a
6,000 (1,800 m)
characteristic impedance of
120 ohms
Twisted, shielded pair
50 (15 m)
Maximum loop wire
2,500 (760 m)
resistance is 40 ohms for the
MMF-300 and 20 ohms for
the MMF-301
No more than a 2.4 volt drop
2,500 (760 m)
allowed at end of circuit.
Maximum loop wire
resistance is 25 ohms
In alarm, no more than a 1.2
Distance limitation
volt drop allowed at end of
set by 1.2 volt
circuit
maximum line
drop
No more than 1.2 volt drop
Distance limitation
allowed from supply source
set by 1.2 volt
to end of any branch
maximum line
drop
No more than 1.2 volt drop
Distance limitation
allowed from supply source
set by 1.2 volt
to end of any branch
maximum line
drop
20 (6 m)
2
12 AWG (3.25 mm
) in
conduit
WIRE REQUIREMENTS
Wire Gauge and Compatible Brands
12 AWG (3.25 mm
Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm
Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S
12-18 AWG (3.25 - 0.75 mm
18 AWG (0.75 mm
18 AWG (0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
Correlations
2
): Genesis 4410,
2
):Genesis 4408 & 4608
2
): Genesis 4406 & 4606
2
): Genesis 4402 & 4602
2
)
2
)
2
) minimum
2
)
2
)
2
)
2
)
2
)
2
)