Operating Instructions
READ STATUS
1=SYSTEM POINT
2=ZONES

3=POWER

Read Status Screen #1
124
4.22.1 System Point
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be
displayed:
READ SYSTEM POINT
1=LOOP 1
2=LOOP 2
The operator selects the loop containing the device to be read by pressing 1 for Loop 1
or 2 for Loop 2. The following screen will then be displayed:
READ SYSTEM POINT
1=DETECTOR
2=MODULE
The operator now selects the type of device which is to be viewed by pressing 1 for
Detector or 2 for Module. If 1 is pressed, the display will change to the following
screen:
READ SYSTEM POINT
ENTER DETECTOR#
***
Entering the three digit detector address will cause the control panel to display the
current status of the selected device. For example, if a detector with address 001 on
loop 1 is entered, a display similar to the following will appear:
NORMAL SMOKE(PHOTO)
The information in the preceding display includes:
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector
(could also be ION for ionization smoke detector)
NORTH CLASSROOM - the Adjective/Noun label for this device
Z005 - the first of five possible assigned software zones
1D001 - 1 = Loop 1, D = Detector, 001 = Address 001
SELECT LOOP
SELECT TYPE
NORTH CLASSROOM
Z005
1D001
Read Status
MS-9600 PN 51335:E 7/9/03