Powering On A Dc-Powered Srx5600 Services Gateway - Juniper SRX5600 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5600:
Table of Contents

Advertisement

Related
Documentation

Powering On a DC-Powered SRX5600 Services Gateway

Copyright © 2014, Juniper Networks, Inc.
Chapter 9: Grounding and Providing Power to the SRX5600 Services Gateway
Figure 42: Connecting DC Power to the Device
Preventing Electrostatic Discharge Damage to the SRX5600 Services Gateway on
page 195
Overview of Installing the SRX5600 Services Gateway on page 39
Tools and Parts Required for SRX5600 Services Gateway Grounding and Power
Connections on page 71
Grounding the SRX5600 Services Gateway on page 72
Powering On a DC-Powered SRX5600 Services Gateway on page 79
Powering Off the SRX5600 Services Gateway on page 81
To power on a DC-powered services gateway:
Verify that an external management device is connected to one of the Routing Engine
1.
ports (
AUX
,
CONSOLE
, or
Turn on the power to the external management device.
2.
Verify that the power supplies are fully inserted in the chassis.
3.
Verify that the source power cables are connected to the appropriate terminal: the
4.
positive (+) source cable to the return terminal (labeled
(–) source cable to the input terminal (labeled
Switch on the dedicated customer site circuit breakers to provide power to the DC
5.
power cables. Follow your site's procedures.
Check the
INPUT OK
LED is lit steadily green to verify that power is present.
6.
ETHERNET
).
–48V
RETURN
) and the negative
).
79