A.1 Heavy Duty and Normal Duty Ratings
A.1 Heavy Duty and Normal Duty Ratings
The capacity of the drive is based on two types of load characteristics: Heavy Duty (HD) and Normal Duty (ND).
Refer to Selecting the Appropriate Load Rating on page 162
capacity ratings are listed on the following pages.
Setting Parameter
Rated Output Current
C6-01
HD Rating
0: Heavy Duty
(default)
varies by model
ND Rating
1: Normal Duty
varies by model
<1> The following pages list information on rating changes based on drive model.
• HD and ND: HD refers to applications requiring constant torque output, while ND refers to applications
TERMS
TERMS
with variable torque needs. The drive allows the user to select HD or ND torque depending on the application.
Fans, pumps, and blowers should use ND (C6-01 = "1"), and other applications generally use HD (C6-01
= "0").
• Swing PWM: Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor noise into a
less obtrusive white noise.
Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, carrier frequency,
and current limit. The default setting is for HD (C6-01 = 0).
162
Table A.1 Selecting the Appropriate Load Rating
150% rated output current for 60 s
<1>
120% rated output current for 60 s
<1>
varies by model
for the differences between HD and ND. Specifications for
Overload Tolerance
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Default Carrier Frequency
8/10 kHz
varies by model
2 kHz, Swing PWM