5.6 H: Terminal Functions
Setting Examples
• Gain H3-03 = 200%, A1 as frequency reference input:
An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency
reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will
be equal to E1-04 above 5 Vdc.
Figure 5.29 Frequency Reference Setting by Analog Input with Increased Gain
• Bias H3-04 = -25%, A1 as frequency reference input
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0 the minimum frequency reference is 0% between 0 and 2.5 Vdc input. An analog input of
2.5 to 10 Vdc will now be the same as 0 to 100% of the frequency reference span.
When parameter H3-01 = 1, the motor will rotate in reverse between 0 and 2.5 Vdc input.
Figure 5.30 Frequency Reference Setting by Analog Input with Negative Bias
• Gain = 0%, Bias = 100%, A1 as frequency reference input
This setting leads to an inverse-acting frequency reference. The minimum analog input level (0 Vdc) will produce a
100% frequency reference and the maximum analog input level (10 Vdc) will produce a 0% frequency reference.
Figure 5.31 Frequency Reference Setting by Analog Input with Inverse Gain and Bias Settings
100
Gain = 100 %
Frequency
reference
Bias = 0 %
0 V
Figure 5.28 Analog Input A1 Default Characteristics
Gain = 200 %
Frequecny
reference
100 %
E1-04
Bias = 0 %
0 V
Gain = 100 %
Frequency
H3-01 = 0
reference
0
Bias = -25%
Bias = 100 %
Frequency
reference
Gain = 0 %
0 V
10 V
5 V
10 V
2.0 V
10 V
H3-01 = 1
10 V