Advertisement

5.7 L: Protection Functions
No.
L3-05
Note: When output frequency is 6 Hz or less, Stall Prevention During Run is disabled regardless of the setting in L3-05/06.
Setting 0: Disabled
Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL
fault.
Setting 1: Decelerate Using C1-02
If the current exceeds the Stall Prevention level set in parameter L3-06, the drive decelerates at Decel Time 1 (C1-02).
Once the current level drops below the value of L3-06 minus 2% for 100 ms it accelerates back to the frequency reference
at the active acceleration time.
Setting 2: Decelerate Using C1-04
Same as setting 1 except the drive decelerates at decel time 2 (C1-04).
n
L3-06: Stall Prevention Level During Run
Sets the current level for Stall Prevention During Run. Depending on the setting of parameter L3-23 the level is
automatically reduced in the constant power range (speed beyond base speed).
No.
L3-06
<1> The upper limit and default for this setting is determined by C6-01 and L8-38.
u

L4: Speed Agree

These parameters set up the speed agree and speed detection functions which can be assigned to the multi-function output
terminal MA-MB-MC.
n
L4-01: Speed Agreement Detection Level
Parameter L4-01 sets the detection level for the digital output functions "Speed Agree," "Frequency Detection 1," and
"Frequency Detection 2."
No.
L4-01
Refer to H2-01: Terminal MA/MB/MC Function Selection on page
n
L4-07: Speed Agreement Detection Selection
Determines when frequency detection is active using parameter L4-01.
No.
L4-07
Setting 0: No Detection During Baseblock
No detection.
Setting 1: Detection Always Enabled
Detection always enabled.
n
Notes on Controlling the Brake for the Hoist Application
• The frequency detection function is used for controlling the brake.
When an external Baseblock command is present while a Run command is active, the frequency reference will be kept
as long as the Run command is active. To avoid improper brake operation make sure that frequency detection is set so
that the brake does not open during Baseblock (L4-07 = "0", default).
Brake Open/Close
Function
Frequency
Detection
Conditions
Frequency
Detection 2
<1>If the load slips during stop, make it greater than E1-09 or 2.0 Hz until the load no longer slips.
106
Name
Stall Prevention Selection During Run
Name
Stall Prevention Level During Run
Name
Speed Agreement Detection Level
Name
Speed Agreement Detection Selection
Parameter
L4-07 = 0
Frequency Detection Level
H2-01 = 5
Frequency Detection Width
Setting Range
Setting Range
30 to 150
Setting Range
0.0 to 400.0 Hz
95, Settings 2, 4, and 5.
Setting Range
Brake Activation Level
Signal
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Default
0 to 2
Default
<1>
<1>
Default
0.0 Hz
Default
0 or 1
Parameter
L4-01 = 2.0 to 3.0 Hz
2.0 Hz (fixed)
1
0
<1>