Output Terminals
8.3

Digital Outputs

Description
Four bi-directional digital outputs (terminal X541) and two relay outputs (terminal
X542) are available. These outputs are, for the most part, freely parameterizable.
Signal Flow Diagram
1 = Ready to start
r0899.0
1 = Ready to operate
r0899.1
1 = Operation enabled
r0899.2
...
1 = Ramp-up/
ramp-down completed
r2199.5
Fig. 8-3
Signal flow diagram: Digital outputs
Factory Setting
Digital output
DO0
DO1
DI/DO8
DI/DO9
DI/DO10
DI/DO11
8-6
p4030
p4031
p4038
p4039
p4040
p4041
Terminal
X542: 2,3
X542: 5,6
X541: 2
X541: 3
X541: 4
X541: 5
Invert
p4048.0
0
1
DO 0
p4048.1
1
1
DO 1
+
p4048.8...11
DI/DO 8
DI/DO 9
DI/DO 10
1
DI/DO 11
M
Factory Setting
"Enable pulses"
"No fault"
"Ready to start"
"LOCAL mode active"
"Enable pulses"
11/03
X542
1
2
3
4
5
6
X541
1
2
3
4
5
6
SINAMICS G150