Analog Inputs - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Operation
6.3.2

Analog Inputs

Description
The customer terminal block features two analog inputs for specifying setpoints via
current or voltage signals. In the factory setting, analog input 0 (terminal X521:1/2)
is used as the current input.
Prerequisite
p1070 = r4055[00]
Proposed Connection Assignment
PROFIBUS/
terminal block
20 mA = n max
ON/OFF1
Fault ack.
Fig. 6-8
6-20
Main setpoint is specified by analog input 0
<MENU> - <parameterization> - <all parameters> - Select
p1070 and set to r4055 - Select index [00]
-A10 (CU 320)
-A60 (TM31)
X540
+
1
1: Terminal
block
X530
1
DI 4
user wiring
X521
S5.0
1
AI 0+
2
AI 0-
3
AI 1+
(p2000)
4
AI 1-
5
P10
6
M
7
N10
8
M
X520
1
DI 0
2
DI 1
3
DI 2
4
DI 3
5
M1
6
M
Proposed connection assignment
~ ~
=
=
~ ~
M
~
11/03
SINAMICS G150
Operating Manual