Siemens SINAMICS G150 Operating Manual page 225

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

11/03
Table 12-18 Version C, 660 V – 690 V, part 2
Category
Order no. 6SL3710-
Rated motor output
Rated connection voltage
Rated input current
Rated output current
Base load current
Power loss
Cooling air requirement
Sound pressure level at 50/60
Hz
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Protective earth connection
Fastening screw
Approx. weight (standard
version)
Dimensions (w x h x d)
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
SINAMICS G150
Operating Manual
Unit
1GH31-5CA0
kW
132
V
3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
A
174
A
150
A
140
kW
2.8
m³/s
0.17
dB(A)
67/68
2
mm
95
(4/0)
2
mm
2 x 240
2 x (600)
M12 (1 hole)
2
mm
95
(4/0)
2
mm
2 x 150
2 x (400)
M12 (1 hole)
M12 (2 holes)
kg
225
mm
400 x 2000 x 600
3NE1 225-2
A
200
1
Technical Data
1GH31-8CA0
1GH32-2CA0
160
200
201
234
175
215
171
208
3.8
4.2
0.36
0.36
69/73
69/73
120
2 x 70
(300)
2 x (000)
2 x 240
2 x 240
2 x (600)
2 x (600)
M12 (1 hole)
M12 (1 hole)
120
2 x 70
(300)
2 x (000)
2 x 150
2 x 150
2 x (400)
2 x (400)
M12 (1 hole)
M12 (1 hole)
M12 (2 holes)
M12 (2 holes)
300
300
400 x 2000 x 600
400 x 2000 x 600
3NE1 227-2
3NE1 230-2
250
315
1
1
12-17

Advertisement

Table of Contents
loading

Table of Contents