Siemens SINAMICS G150 Operating Manual page 84

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Operation
Control Sources
The system can be controlled via the operator panel, terminal block, or PROFIBUS.
Control via PROFIBUS
Cabinet operator panel
PROFIBUS
PROFIBUS /
Terminal block
LOCAL disable
Terminal block
Fig. 6-1
Control sources
Priority
The priority of the control sources is shown in Fig. 6-1.
NOTE
Emergency OFF signals (L57, L59, L60) and motor protection signals (L83, L84)
are always active (regardless of the control source).
6-2
"LOCAL/REMOTE" key
0
1
r0050 - Active CDS
0: PROFIBUS - REMOTE 0
1: Terminal block - REMOTE 1
X530.1
X530.2
LOCAL disable
LOCAL disable
&
r0807 - Master control active
0: REMOTE -
PROFIBUS / Terminal block
1: LOCAL - Operator panel
1
internal controller
0
11/03
SINAMICS G150
Operating Manual

Advertisement

Table of Contents
loading

Table of Contents