Diagnosis Via Parameters - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Diagnosis / Faults and Alarms
10.2.2

Diagnosis via Parameters

Diagnostic Parameters for the Device Status
r0002
Drive status
Display of drive status.
r0046
Missing enable signals
Display of the missing enable signals.
Bit 00: Enable OFF1
Bit 01: Enable OFF2
Bit 02: Enable OFF3
Bit 03: Operation enabled
Bit 08: Enable SH
Bit 09: Enable infeed
Bit 10: Enable ramp generator
Bit 11: Ramp generator start
Bit 12: Enable setpoint
Bit 17: Int. enable OFF2
Bit 18: Int. enable OFF3
Bit 21: Int. enable STOP2
Bit 27: Demagnetization
Value 0 indicates that all the enable signals for this drive are present.
Bit 00 = 1 (no enable) when:
Bit 01 = 1 (no enable) when:
Bit 02 = 1 (no enable) when:
Bit 03 = 1 (no enable) when:
Bit 08 = 1 (no enable) when:
Bit 09 = 1 (no enable) when:
Bit 10 = 1 (no enable) when:
Bit 11 = 1 (no enable) when:
Bit 12 = 1 (no enable) when:
Bit 17 = 1 (no enable) when:
Bit 18 = 1 (no enable) when:
Bit 21 = 1 (no enable) when:
Bit 27 = 1 (no enable) when:
10-4
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: present
1: missing
0: complete
1: not complete
The signal source in p0840 is set to 0 signal.
Power-on disable is present.
The signal source in p0844 or p0845 is set to 0 signal.
The signal source in p0848 or p0849 is set to 0 signal.
The signal source in p0852 is set to 0 signal.
No pulse enable on the motor module (X21.3, X21.4)
The signal source in p0864 is set to 0 signal.
The signal source in p1140 is set to 0 signal.
The signal source in p1141 is set to 0 signal.
The signal source in p1142 is set to 0 signal.
Commissioning mode is set (p0009 > 0 or p0010 > 0).
OFF3 or fault reaction OFF3 is not yet complete.
The bit is reset with the power-on disable function.
The holding brake is applied or has not yet been released.
The motor is not yet magnetized.
Demagnetization is not yet complete.
11/03
SINAMICS G150
Operating Manual