Furuno NAVpilot-611 Installation Manual page 31

Autopilot
Hide thumbs Also See for NAVpilot-611:
Table of Contents

Advertisement

3.2.2 Selecting the type of rudder reference unit
Select the type of your rudder reference unit at here.
1. Rotate the course control knob to select "SELECT RRU", and then press the course
control knob.
The select RRU options window appears.
2. Rotate the course control knob to select ROTARY SENSOR or LINEAR SENSOR.
ROTARY SENSOR: The rudder reference unit FAP-6111 is connected.
LINEAR SENSOR: The Teleflex
3. Press the course control knob to close the window.
Note: When selecting LINEAR SENSOR, change the JP2 position certainly referring to
page 2-4.
3.2.3 Bleeding air in the oil cylinder
Always confirm that all of the air is bled from the steering system by moving the rudder
automatically or manually.
1. Rotate the course control knob to select "AIR BLEEDING", and then press the course
control knob to show the air bleeding options window.
There are modes to bleed air from the system. The arrow key mode allows you to control the
pump motor to bleed the system directly from the Navpilot control unit. The RRU mode
allows you to turn the rudder reference arm in the lazaretto or steering gear room to control
the pump motor remotely.
2. Rotate the course control knob to select USE ◄► KEYS or USE RRU as appropriate.
3. Press the course control knob to show the rudder indicator.
ROTARY SENSOR
LINEAR SENSOR
Select RRU options window
®
linear sensor AR4102 or AR4302 is connected.
WARNING
Confirm that no one is near the rudder
when bleeding air from oil cylinder.
The rudder may move unexpectedly,
possibly causing bodily injury.
NO
USE
USE RRU
Air bleeding options window
KEYS