10-1. Safety Cautions

The indoor unit shall be installed so that the top of the indoor unit is positioned
at least 2 m high.
Also, avoid putting anything on the top of the indoor unit.
2 m
or more
CAUTION
Install in rooms that are 13 m³ or larger.
If a leak of refrigerant gas occurs inside
the room, an oxygen deficiency can occur.
[6] Remote controller holder mounting screw
• With the remote controller cover removed,
correctly load the supplied batteries while observing their polarity.
• If the system will be used in cooling mode when the outdoor temperature is below zero, take measures to
ensure that the drain water does not freeze.
• When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a
high story of a building, secure the normal fan operation using a duct or a wind shield.

10. INSTALLATION PROCEDURE

Hook
160 mm or more
[5] Mounting screw
Hook
Air filters
[2] Wireless remote controller
[4] Remote controller holder
Before installing the wireless remote controller
70 mm or more
Hook
[1] Installation plate
180 mm
or more
Hook
Connecting
cable
[Z] Shield pipe
(for extension drain hose)
[2] Wireless remote controller
– 74 –
For the rear left and left piping
Wall
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
installation work.
Do not allow the drain hose
to become slack.
Cut the piping hole
slightly sloped
Make sure the drain hose is
sloped downward.
The auxiliary piping can be
connected at the left, rear left,
rear right, right, bottom right
or bottom left as shown below.
Right
Rear right
Rear left
Bottom right
Bottom left
Insulate the refrigerant pipes
separately, not together.
8 mm thick heat resisting
polyethylene foam
Cover
[3] Batteries
Left