Toshiba RAS-M16PKVP-E Service Manual page 108

Air-conditioner split type
Hide thumbs Also See for RAS-M16PKVP-E:
Table of Contents

Advertisement

Check
Outdoor
code
LED display
[1C]
l
l
ll
¡
¡
(Item without special mention indicates part of outdoor unit.)
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P .C. board to judge which error it is.
Compressor system error, Compressor lock, Gas side temp. sensor (TGa to TGe)
error, Gas leakage, PMV error
[Compressor system error, Compressor lock]
Is AC mains voltage correct?
(198 to 264V)
YES
Is wire connection correct?
Compressor lead
(Board side, Compressor Side),
Reactor lead, Power supply lead.
YES
Is compressor under correct condition?
NO
Is there refrigerant stagnation?
YES
Does PMV correctly operate?
YES
1
1
Are the power devices on P.C. board
MCC-1571 screwed without looseness?
(Rear sides of Q201, Q300, Q650, DB01, DB02)
Are radiation grease properly applied?
(Q201)
YES
Does something block
the ventilation around the heat sink?
Does something air flow from the fan?
NO
– 108 –
Check and troubleshooting
NO
NO
YES
NO
NO
NO
Apply radiation grease to objective parts.
Retightening of screws.
(Be sure not to forget to attach insulating sheet
between heat sink and Q300, Q650, DB01, DB02)
YES
Check outdoor P.C.B MCC-1571 and MCC-5071.
Defect → Replace
Check wiring construction.
Ask repair of power supply.
Check wire connection
and correct it.
1
Compressor lock → Replace.
Check TE, TS sensor and PMV.
Detect →
Replace..
Remove blocking matter.
Correct short-circuit.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents