Clean Operation Cancel - Toshiba RAS-M16PKVP-E Service Manual

Air-conditioner split type
Hide thumbs Also See for RAS-M16PKVP-E:
Table of Contents

Advertisement

Item
17. Clean operation
Setting the clean operation cancel
Setting the clean operation
Indoor P.C. board
Operation flow and applicable data, etc.
Add J231 of the wireless unit P.C. board assembly.
∗ This cancels the auto restart function.
Hold down the [RESET] button on the indoor unit for
at least 3 seconds but not more than 10 seconds.
The indoor unit's buzzer emits three beeps.
This completes the clean operation cancel setting.
Hold down the [RESET] button on the indoor unit for
at least 3 seconds but not more than 10 seconds.
The indoor unit's buzzer emits three beeps, and
the OPERATION indicator flashes at 5 Hz intervals.
This completes the clean operation setting.
IC231
J231
– 66 –
Description
CAUTION
J231 will be near the MCU so
take steps to ensure that it will
not be exposed to excessive
levels of heat.
Also take care to avoid solder
bridging with the surrounding
components.
NOTE
Once J231 is added, the [RESET]
button on the unit is designated for
CLEAN OPERATION (Set/Cancel),
therefore the [RESET] button can
not be used for the selection
(Set/ Cancel) of AUTO RESTART
function (Refer to 9-3. Auto
Restart Function).