10-1. Installation Diagram of Indoor and Outdoor Units
Mounting
5
Filter
Flat head
7
wood screw
Remote control
4
holder
Wireless
2
remote control
Before installing the wireless remote controller
• Loading Batteries
1. Remove the slide cover.
2. Insert 2 new batteries (AAA type)
following the (+) and (-) positions.
10-2. Installation
10-2-1. Optional installation parts
Part
Parts name
code
Refrigerant piping
Liquid side : Ø6.35 mm
A
Gas side
: Ø9.52 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C

10. INSTALLATION PROCEDURE

Hook
6
screw
Hook
Vinyl tape
Apply after carrying
out a drainage test.
3
Batteries
2 Wireless remote controller
Q'ty
One
each
One
each
Hook
Installation
1
plate
Shield pipe
3 Batteries
1
- 57 -
For the rear left and bottom left piping
Wall
Cut out a piece of SPACER from indoor unit
packaging box, roll it and insert between
the indoor unit and wall to tilt the indoor unit
for better operation.
The auxiliary piping can be connected
to rear left, rear right, bottom right or
bottom left.
Rear
right
Bottom
Rear
right
left
Bottom left
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
Make sure to run the drain hose sloped
downward.
Refrigerant piping must be protected
from physical damage.
Install a plastic cover or equivalent.
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm thick heat resisting
polyethylene foam