Vertical, Interior, Typical Installation; Through The Wall & Vertical, Exterior - Heatilator PT60 Owner's Manual

Zero clearance pellet fireplace installation and operation
Table of Contents

Advertisement

POINTE Pellet Fireplace
J. Vertical - Interior - Typical Installation
Flashing
Firestop
6 in.
(152mm)
Min.
Non-combustible
Hearth Extension
Figure 44.1
Page 44
Termination
Cap
12 in.
(305mm)
Minimum
1 in. (25mm)
Minimum
*See Note
0 in. (0mm) to
Standoff
6 in. (152mm)
minimum
Non-combustible
Hearth Extension
Figure 44.2
7051-507
We recommend a minimum of 60 inches (1.52m) verti-
cal, however above the eave is preferred.
Both installations are approved for mobile home instal-
lations. Must use 3 or 4 inch (76mm to 102mm) "L"
or "PL" Listed pellet venting or Listed double wall pipe
and Quadra-Fire Outside Air Kit in all installations.
Single wall pipe is approved for residential installa-
tions only.
*NOTE: Clearance to combustibles are for 1 inch
(25mm) clearance approved pellet pipe. If pellet pipe
has a 2 inch or 3 inch (51mm or 76mm) air clearance
to combustibles, increase the clearance from rear
standoff accordingly to meet pipe manufacturer clear-
ance requirements
K. Through the Wall & Vertical - Exterior
Flashing
0 in. (0mm) to Standoff
Termination
Cap
12 in.
(305mm)
minimum
Support
Bracket
every 60 in.
(1524mm)
Wall Thimble
Tee
Clean-out
Cover
April 29, 2011