Model
Method
Operation method
Cooling method
Input
Rated input voltage
Input
Sensitivity setting: Standard
voltage
Sensitivity setting: Low
range
Sensitivity setting: High
Input maximum current
Frequency
Phase
Input protection
AC input plug
Output
Rated output capacity
Voltage
Commercial operation
Backup operation
Frequency Commercial operation
Backup operation
Waveform Commercial operation
Backup operation
Distortion rate *3
Phase
Output receptacles
Battery
Type
Voltage / Capacity x Quantity
Backup time
(25°C, initial characteristics)
Charging time *7
Battery life Ambient temperature
25°C
Environment Operating environment temperature/
humidity
Storage temperature
Safety standard / RoHS directive
compliance
Disturbance voltage / Radiated
interference field strength
Internal power consumption (normal/
maximum)
Noise
Dimensions (W x D x H)
Weight of unit
*1 For BN150R, the maximum output (1.5kVA/1.35kW) cannot be used with the standard input plug (NEMA 5-15P). To use with maxi-
mum output, replace with a 20A plug. (A 20A plug is included in the accessories.)
*2 For BN300R, the maximum output (3.0kVA/2.7kW) cannot be used with the standard input plug (NEMA L5-30P). To use with maxi-
mum output, connect to the terminal block (purchased separately).
The standard equipment input plug (NEMA L5-30P) cannot be connected to a household receptacle.
*3 Rectified load, rated load, in Battery Mode (except in BL state)
*4 Rated load/ Rated input voltage/ When fully charged
*5 Rated load/ Rated input voltage/ When battery charge current is at maximum
BN75R
Line-interactive method
Forced air cooling
89±3 to 118V±3 VAC
84±3 to 118V±3 VAC
89±3 to 113V±3 VAC
12A
Single-phase, two-wire (grounded)
NFB(13A)
3P (NEMA 5-15P)
3P (NEMA 5-15P) *1
750VA/680W
1500VA/1350W *1
90±3 to 114V±3 VAC (Sensitivity setting: Standard)
84±3 to 114V±3 VAC (Sensitivity setting: Low)
90±3 to 110V±3 VAC (Sensitivity setting: High)
Synchronized with input frequency
20% max. (Rectified load, at rated output)
15% max. (Resistance load, at rated output)
Single-phase, two-wire (grounded)
NEMA 5-15R x 4
Sealed lead battery
6 V / 9 Ah × 4
4 min. or more
Expected life: 5 years
0°C to 40°C, 25 to 85%RH with no condensation
-15°C to 50°C, 10 to 90%RH with no condensation
UL1778 / RoHS compliant / CE
50W (*4) / 100W (*5)
100W (*4) / 200W (*5)
38 dB max.
438mm x 512mm x 43mm
438mm x 437mm x 87mm
Approx. 13.5kg
BN150R
BN300R
100 VAC
20A
50/60Hz±4Hz
NFB(25A)
NFB(45A)
3P (NEMA L5-30P) *2
3000VA/2700W *2
100 VAC±6%
50/60Hz±0.1Hz
Sine wave
Sine wave
NEMA 5-15R x 6
NEMA 5-15R x 6
NEMA 5-20R x 2
12 V / 9 Ah × 4
12 V / 9 Ah × 6
4.5 min. or more
2.5 min. or more
4 hours 90%
VCCI Class A
150W (*4) / 300W (*5)
50 dB max.
50 dB max.
438mm x 650mm x 87mm
Approx. 21.5kg
Approx. 32kg
40A
66