2-4-1. Connecting the AC input plug
BN75R connection procedure
Provide a wall outlet (commercial power) suitable for the shape of the 15A plug (NEMA 5-15R).
It is possible to connect to a 2-pin outlet using the included 3P-2P adapter.
In this case, provide grounding separately.
BN150R connection procedure
When using the 15A plug (connected when shipped)
-
Provide a wall outlet (commercial power) suitable for the shape of the 15A plug (NEMA 5-15R).
It is possible to connect to a 2-pin outlet using the included 3P-2P adapter.
In this case, provide grounding separately.
When using the 20A plug
You can use up to the rated capacity of the BN150R.
-
Provide a wall outlet (commercial power) suitable for the shape of the 20A plug (NEMA 5-20R).
- Replace the AC input plug with the included NEMA L5-20P plug.
Plug replacement procedure
(1) Disconnect the 15A plug.
(2) Connect the included NEMA L5-20P plug as shown in the illustration below.
Make sure the wire colors match those in the diagram before tightening the
screws
BN300R connection procedure
When using the 30A plug (connected when shipped)
-
Provide a wall outlet (commercial power) compatible with the shape of the 30A plug (NEMA L5-
30R).
- If this plug is used, make sure that the capacity of the connected devices stays below the maxi-
mum capacities shown in the table on page 17.
- After connecting to commercial power, turn ON the INPUT PROTECTION switch (input overcur-
rent protection switch) on the back of the unit.
L: Black
FG: Green
75
150
BN
R/BN
N: White
300
R/BN
R
2
18