Page 1
Uninterruptible Power Supply UPS BA75T/BA100T/BA100R Instruction Manual 使用说明书 BA75T/BA100T BA100R ・ This manual provides important safety-related information. Thoroughly read and understand this manual before installing and using the product. ・ Keep this manual in a convenient location so that you can refer to it whenever necessary.
This is especially suitable for use where power supply conditions are poor (for example, when there are large variations in voltage) ● Output capacity is 750VA/600W for BA75T, 1000VA/800W for BA100T/BA100R. Notes on the use of the Backup Power Supply ●...
Introduction IMPORTANT SAFETY INSTRUCTION 1. SAVE THESE INSTRUCTIONS. This manual contains important instructions for BA75T/BA100T/BA100R that should be followed when using the UPS and batteries. 2. SYMBOL This symbol indicates earth ground. This symbol indicates turning on/off UPS. 3. INTERNAL BATTERY Internal battery voltage is 24VDC for BA75T/BA100T/BA100R.
We recommend charging the UPS before using it. Operate 3. Check and start operation Perform maintenance and inspection Perform maintenance and inspection The battery must 4. Maintenance and Inspection be replaced Replace the battery 4.2 Replacing the battery BA75T/BA100T/BA100R...
3-3-1 Start and stop procedures ....................44 Interpreting beeps and displays ..............46 3-4-1 Displays and beeps in normal operations ................46 3-4-2 Displays and beeps while testing ..................47 3-4-3 Displays and beeps during power failure or AC input error ..........47 BA75T/BA100T/BA100R...
Page 6
6-1-4 Remote ON/OFF port ......................83 6-1-5 Contact Signal ratings ......................83 6-1-6 Contact Signal circuit ......................83 6-1-7 Example of the use of the Contact Signal circuit ..............84 6-1-8 Precautions and notes for the use of the Contact Signal ........... 84 BA75T/BA100T/BA100R...
Page 7
Table of Contents 7 Troubleshooting ..................85 8 Note of Chinese ..................86 9 References ................... 95 Specifications ....................95 Dimensions ..................... 96 Battery life ..................... 101 China RoHS Information ................102 BA75T/BA100T/BA100R...
This is a Class A product based on the standard of the VCCI Council. If this equipment is used in a domestic environment, radio interference may occur, in which case, the user may be required to take corrective actions. BA75T/BA100T/BA100R...
Page 9
● Dropping or toppling the unit may cause injury. ● The approximate weight of the unit is 12.5 kg (BA75T/BA100T), 13 kg (BA100R). ● If you drop the unit, stop using it and have it inspected and repaired.
Page 10
● Mounting screws other than those included may not be strong enough to support the unit, causing it to fall. ● If you attach the case using long screws other than those included with the product, you may damage the internal parts of the unit. BA75T/BA100T/BA100R...
Page 11
Do not place any objects on the unit, and do not drop heavy objects onto the unit. ● Doing so may cause distortion/damage to the case or a failure of the internal circuit, which may cause a fire. BA75T/BA100T/BA100R...
Page 12
(for battery replacement) Perform replacement on a stable and flat place. ● Handle the battery carefully so that you do not drop it. ● Risk of injury due to falling, or burns due to fluid leakage (dilute sulfuric acid). BA75T/BA100T/BA100R...
Page 13
● Battery pack for: Product model: BAB100R: Battery pack for BA100R BAB100T: Battery pack for BA75T/BA100T Do not replace the battery in a place where there is flammable gas. ● Spark may occur when connecting the battery, which may cause an explosion or fire.
Page 14
: Déterminer si la pile est mise à la terre. Si elle est mise à la terre, effectuer la deconnection. Le contact avec une pile mise à la terre peut créer un choc électrique. Ceci sera réduit si cette mise à la terre est supprimée pendant installation et maintenance. BA75T/BA100T/BA100R...
Page 15
● This manual contains important safety-related information. Please read and understand the contents of the manual before beginning operation. If this manual is misplaced, download the manual from our website. BA75T/BA100T/BA100R...
Page 16
● Turn OFF the unit’s “Power” switch when storing it. Do not install or store the unit in a place exposed to direct sunlight. ● The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable. BA75T/BA100T/BA100R...
1-1 Unpacking the product Caution (for installation and connection) The approximate weight of the unit is 12.5 kg (BA75T/BA100T), 13 kg (BA100R). Note the weight when unpacking and transporting the unit. ● Dropping may cause injury. Open the package box and take out the UPS and accessories.
1 Preparation 1-3 Related products 1-3 Related products Description Model Number Replacement battery pack for BA75T/BA100T BAB100T *1 Replacement battery pack for BA100R BAB100R *1 Input power cable BAX15NP Replacement fan BAF100R Support angles compatible with EIA/JIS 19-inch racks BAP100RS *2...
This section describes the name of each part of the UPS. For information on the function of each part, refer to “2 Installation and connection” and “3 Check and start operation” that provides the details. ● Front view <BA75T/BA100T> (Air vent) (Operation panel) <BA100R> (Air vent) (Operation panel) <Enlarged view of the operation panel>...
1 Preparation 1-4 Name of each part ● Rear view <BA75T/BA100T> A: RS232C port B: Contact signal port C: Remote ON/OFF port D: Input protection E: AC input terminal block F: AC output terminal block G: Input surge protection GND H: Power supply output receptacles (Backup is performed during power failure.)
(high power Noise input (sine factor filter wave) Input Power converter) overcurrent supply protection relay Output switching (4 ms. max.) Step-up converter Control Power supply Charging circuit switch circuit At startup/capacity exceeded/error Battery During Line mode During Battery mode BA75T/BA100T/BA100R...
● Allow sufficient space at the back for the AC input cables of the UPS unit and connected devices. <BA75T/BA100T> Correct Positions Ba careful not to get your fingers caught when arranging the unit.
Page 24
2 Installation and connection 2-1 Installation <BA100R> Correct Positions Ba careful not to get your fingers caught when arranging the unit. Note: Upright stand for BA100R, BAP100R, is necessary for (Air vents are facing upward) this position. Incorrect Positions BA75T/BA100T/BA100R...
Rail length fixing screws (M4 x 8) ........4 Ear bracket mounting flat-head screws (M3 x 6) ....8 EIA/JIS rack fixing screws (M5 x 16) ........10 JIS rack fixing flat-head screws (M5 x 14) ......2 EIA rack fixing nuts (M5) ............. 10 BA75T/BA100T/BA100R...
Page 26
EIA/JIS rack fixing screws (M5) at 2 rear positions. (3 The screw hole position for the front is at the second screw hole from the top, the rear is at the second screw hole from the bottom. Adjust the length to suit the server rack and tighten securely Rack fixing screws BA75T/BA100T/BA100R...
Page 27
Place the UPS on the support angles and push it completely into the rack (5, and use the 2 included EIA/JIS rack fixing screws (M5) to securely fasten the ear brackets to the server rack. (6 Push completely in Use the unit fixing screws to fasten Be sure to use the support angles. BA75T/BA100T/BA100R...
Attach the included rubber feet for horizontal installation and position the unit horizontally. For stationary horizontal installation, make sure that this product does not slide or fall. ● Upright installation Use the upright stands (2) and M3 flat-head screws (6) included with the rated product. BA75T/BA100T/BA100R...
Page 29
2 Installation and connection 2-1 Installation ■ BA75T/BA100T ● Upright installation Use the upright stands (1) and M3 flat-head screws (4) included with the rated product, when you want to fix it. BA75T/BA100T/BA100R...
Connect devices you want to back up to the Power Supply Output Receptacles of the UPS. ・ If you need more output receptacles than those of the UPS, purchase a plug strip and use it for extra output receptacles. BA75T/BA100T Computer peripheral devices External HDD Computer peripheral devices...
Page 31
See also "5 To perform shutdown processing of the devices when a power failure occurs", and "6 Using the contact signal functions" Note: If you do not use the UPS monitoring software and Contact Signal, this step is not required. BA75T/BA100T/BA100R...
(with Type II certification or higher). ● To use the BA100T/BA100R with up to 1000VA/800W, a wiring capacity of 12A or required. To use the BA75T with up to 750VA/600W, a wiring capacity of 10A or required. Make sure to properly match the AC input terminal. Turn off the external breaker when performing work on the unit's AC input terminals.
Page 33
When the installation and connection are complete, connect the input of this unit to a commercial power source such as a power switchboard. When you connect it to a commercial power source, battery charging automatically starts regardless of the ON/OFF state of the “Power” Switch and charging completes within 8 hours. BA75T/BA100T/BA100R...
Page 34
Caution To reduce the risk of fire, ● Connect only to a circuit provided with 15A (for BA100T/BA100R), 10A (for BA75T) maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1 ●...
OFF. Orange “Battery mode” LED Backup is operating. Backup This status is called operating. “Battery Mode”. “Battery replacement” Battery replacement Battery replacement is is necessary due to not necessary. battery deterioration or the end of battery life. BA75T/BA100T/BA100R...
Page 37
(“Setting” switch 3)... Factory setting: OFF OFF: The self-diagnostic test is automatically executed once every 4 weeks. ON: Does not perform the auto test once every 4 weeks. Use this setting to disable Battery Mode for the regularly performed test. BA75T/BA100T/BA100R...
Page 38
Mode A regardless of this setting. 1) When BS signal is used to stop the UPS after a power failure occurs. AC input BS signal Power output (Setting switch 4 OFF: Mode A) Power output (Setting switch 4 ON: Mode B) BA75T/BA100T/BA100R...
Page 40
・ Output voltage: Inverter output in Commercial Power Mode. It is not affected by input voltage. ・ Output frequency: Always output with 60 Hz. It is not affected by input frequency. ・ Bypass output: An output stops without bypass output in the event of failure or overload. BA75T/BA100T/BA100R...
0.5second 2 second 1-second 4-second intervals: intervals: 4second 1 second ● Continuous Continuous ■ Stopping the beep sound When the beep is sounding, you can stop it by pressing and holding the “STOP/TEST” switch for 0.5 seconds or longer. BA75T/BA100T/BA100R...
We recommend charging the UPS before using it. When you connect it to a commercial power source, battery charging automatically starts regardless of the ON/OFF state of the “Power” Switch and charging completes within 8 hours. BA75T/BA100T/BA100R...
Page 43
UPS stop, this may be attributed to an insufficient battery charge. After connecting the AC input to the commercial power and charging the battery for at least 8 hours, go back to step 5. ・ If the problem persists after checking the 2 points above, contact us. BA75T/BA100T/BA100R...
Page 44
Reconnect the AC input to the commercial power source. Status indicator returns to its normal state and the beeping sound stops. (The status is as shown below.) Status indicator Description “Power” switch “ON” Operating normally Checking the operation is now complete. BA75T/BA100T/BA100R...
Power Battery Startup Bypass Self-diagnostic Inverter preparation operation test operation a few a few about 1 sec. seconds seconds 15 sec. <Note> D-1: Display the latest UPS fault mode (If there is no record for UPS fault, UPS display the BA75T/BA100T/BA100R...
Page 46
● When charge of the battery does not remain If a power failure or abnormal power input is resolved after the battery is discharged completely and power output is stopped, the UPS restarts automatically and resumes power output. The expended battery begins to charge. BA75T/BA100T/BA100R...
Charging Description Solution indicator output ment lamp lamp lamp No AC input. None Operation stopped. There is AC input. None “Power” switch is OFF. There is AC input. “Power” switch is OFF, None Connect Battery. or OFF⇒ON. Battery Disconnect. BA75T/BA100T/BA100R...
AC input frequency is None (ON) Use within the AC input too high. voltage/frequency range described in the AC input voltage is too specifications. None (ON) low and AC input frequency is too high. AC input voltage is too None (ON) high. BA75T/BA100T/BA100R...
ON again. Check that the AC input of connected devices is Check that the not short-circuited, or connection capacity has that the connection Continuous (Note 2) not exceeded the rated capacity does not capacity. exceed the rated capacity. BA75T/BA100T/BA100R...
Page 50
DC bypass Bus voltage .(Note 1). Moved to bypass operation due to problem with the half (Same as above.) Continuous (Note 2) bypass wave rectification load (Note 1) (Note 3) External Fan Error. (Same as above.) Continuous (Note 2) BA75T/BA100T/BA100R...
There is a problem with Failure occurred. When the unit. Contact the the “Buzzer shop of purchase or the Pause/Test” switch is OMRON Electronic Continuous pressed, the details of Systems & Equipments the error are displayed. Customer Support Center.
This timing is 10 sec. Power output stop decay 5. BU signal delay setting It is possible to set the delay time of BU signal after AC fail occur. (Setting range: 0 to 90 seconds, Default setting: 0 second) BA75T/BA100T/BA100R...
Page 53
Battery Low signal (BL) Trouble signal (TR) Output signal Backup signal (BU) Deteriorated battery signal (WB) Backup power supply stop signal (BS) Input signal Remote ON/OFF signal Beep While the signal is being input, these status indications blink and the beep sounds. BA75T/BA100T/BA100R...
Maximum backup time Reboot battery voltage BS signal delay BU signal delay Dry contact logic Dry contact test (2) The unit enters the “individual item setting mode” when the “Buzzer Pause/Test” switch is pressed and held (for more than 1 second). BA75T/BA100T/BA100R...
Page 55
("BUT" setting) current setting Backup 0.1 min. Backup 0.2 min. (0.1 min. step) Backup 0.9 min. Backup 1 min. Backup 2 min. (1 min. step) Backup 10 min. Backup 20 min. (10 min. step) Backup 90 min. (next page) BA75T/BA100T/BA100R...
Page 56
Charge 20% (10% step) Charge 90% Delay 0 min. BS signal delay (Default) Display ("DBS" setting) current setting Delay 0.2 min. Delay 0.5 min. Delay 1 min. Delay 2 min. (1 min. step) Delay 10 min. Disable (next page) BA75T/BA100T/BA100R...
Page 57
BL signal Set and display reversed Current state of setting TR signal Current state of WB signal BL signal test Dry contact test Display TR signal test BU signal test WB signal test BS signal test Remote ON/OFF test BA75T/BA100T/BA100R...
・Performed with one time per four weeks on the condition that the “Power” switch is ON When charge of the battery is not completed, the self-diagnosis test is not performed immediately. It is performed automatically after the completion of charge. BA75T/BA100T/BA100R...
・ Graph of backup time (graph of initial values for products that have not been used at 25°C). The backup time becomes shorter than the graph (table) below when temperature is lower. ・ The smaller the capacity of connected devices becomes, the longer the backup time becomes. BA75T/BA100T/BA100R...
Page 60
4 Maintenance and Inspection 4-1 Checking the battery Backup time (25°C, Initial Value) BA75T BA100T/BA100R 120 160 320 360 520 560 720 760 Capacity (W) Backup time table Time unit: (Minutes) BA75T Connection capacity (W) Backup time (Minutes) BA100T/BA100R Connection capacity (W) Backup time (Minutes) Note: These backup times are for reference only.
● Do not replace the battery while the UPS is operating in backup mode. Output will stop. Additional Information When the battery replacement LED lights up/blinks and beeper sounds, press the “Buzzer Pause/Test” switch for 0.5 seconds to stop the beeper. (Lighting/blinking of “battery replacement” LED does not disappear.) BA75T/BA100T/BA100R...
30°C For the first 3 years after starting When 3 years or more have passed after starting use 25°C For the first 4 years after starting When 4 years or more have passed after starting use BA75T/BA100T/BA100R...
For cautions when replacing the battery of the UPS, refer to “Caution for battery replacement)” shown in the "Safety precautions" of the beginning of this manual. ■ BA75T/BA100T Use a hex screwdriver or wrench to loosen (turn counterclockwise) the 2 screws at the top of the front panel of the unit, until they turn freely.
Page 64
Use the red tape on the top of the battery pack, which is 10 cm from the inner edge of the battery, to gauge how much further you need to pull the battery to remove it. Hold the battery securely with both hands so as not to drop it. Red tape Pullout label (Pull this to remove) BA75T/BA100T/BA100R...
Page 65
Insert a new battery into the UPS as far as it will go. ● Replacement battery pack BA75T/BA100T: Model BAB100T Attach the plate cover in order of (1 to (2. Use a screwdriver to securely tighten (clockwise) the screw you removed. (3 Do not pinch the cable with the plate cover.
Page 66
Use a hex screwdriver or wrench to securely tighten (clockwise) the 2 screws at the top of the front panel. (2 Tighten the 2 screws with hex screwdriver or wrench Attach the front panel Battery replacement is now complete. BA75T/BA100T/BA100R...
Page 67
(1 Pull the right side of the front panel towards you to remove it. (2 Pull the right side towards you to remove Loosen the 2 screws with hex screwdriver or wrench BA75T/BA100T/BA100R...
Page 68
Turn the screw that fix the plate cover counterclockwise to remove them. (1 Pull the plate cover right (2 and pull the left side towards you to remove it. (3 Loosen the screw BA75T/BA100T/BA100R...
Page 69
Hold the battery securely with both hands so as not to drop it. Red tape Pullout label (Pull this to remove) Insert a new battery into the UPS as far as it will go. BA75T/BA100T/BA100R...
Page 70
Note: You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this sound is not abnormal. Enlarged view of the connector Connect by Insert the connector’s holding here groove into the holder BA75T/BA100T/BA100R...
Page 71
If you do not reset the battery life counter, a battery deterioration alarm may occur faster than the expected battery life. ・ Stick the related Battery replacement date label on the Unit after writing the battery replacement date. BA75T/BA100T/BA100R...
Do not insert your hand or metal objects into the fan recess. ● Doing so may cause electric shock or short-circuit. Do not put your fingers into the fan. ● The fan spins when connecting the AC input. ● Doing so may result in injury. BA75T/BA100T/BA100R...
4 Replacing the fan 4-3 Replacing the fan 4-3-1 Fan replacement procedure ■ BA75T/BA100T Make sure that UPS doesn't connect to any AC inputs and the fan stops. Use a screwdriver to loosen (turn counterclockwise) and remove the 2 screws on the fan cover above the fan on the back of the unit.
Page 74
Insert the new fan connector until it clicks into place. (3 ● Replacement fan BA75T/BA100T/BA100R: Model BAF100R Insert the fan and the fan guard into the unit’s fan recess. (1 Use a screwdriver to securely tighten (turn clockwise) the 4 removed screws. (2 When doing so, make sure the cable does not become pinned under the fan’s cover.
Page 75
Pull the fan toward you to remove it. (2 Fan guard Fan recess Loosen the 4 screws Pull the fan to remove While pressing left on the tip of the fan connector (1, pull it toward you to disconnect it. BA75T/BA100T/BA100R...
Page 76
Insert the new fan connector until it clicks into place. (3 ● Replacement fan BA75T/BA100T/BA100R: Model BAF100R Insert the fan and the fan guard into the unit’s fan recess. (1 Use a screwdriver to securely tighten (turn clockwise) the 4 removed screws. (2 When doing so, make sure the cable does not become pinned under the fan’s cover.
Stop all the connected devices and the UPS and disconnect the AC input from the commercial power. Then, remove dust with a dry cloth and make the connection again. (For information on the connection procedure: see also "2-2 Connecting the equipment.") BA75T/BA100T/BA100R...
16. SNMP management UPS management information can be sent to the SNMP manager. 17. Telnet connection Settings such as shutdown parameters can be made via the Telnet connection. 18. SYSLOG support UPS management information can be recorded in SYSLOG. BA75T/BA100T/BA100R...
Note: Ensure that your PC completes shutdown within the backup time after a power failure occurs. For the backup time, refer to “4-1-3 Estimated backup time”. For more information, refer to the manual in the CD-ROM. BA75T/BA100T/BA100R...
It can be downloaded from our website, http://www.omron.co.jp/ese/ups/download/category_u.htm. For more information, refer to the manual of this soft ware. 5-2-3 How to connect Connect the UPS to a computer. Cable: Included connection cable (RS232C) <BA75T/BA100T> Connector Connect to RS-232C port on UPS <BA100R>...
Page 82
● If a power failure occurs and then the power is restored while auto shutdown is still in progress, UPS output will stop temporarily after the set time elapses. After shutdown is finished, do not turn on the computer until the UPS has finished restarting. BA75T/BA100T/BA100R...
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10 seconds from the outside. Note 2: Connection terminals are at contact signal port pins 6, 7 and the remote ON/OFF port (See also "3-1-4 Setting Switch"). BA75T/BA100T/BA100R...
Voltage between terminals: 5 VDC Current when closed: 10 mA max. 6-1-6 Contact Signal circuit ● Signal output (BL, TR, BU, WB) ● Remote ON/OFF ● UPS Stop Signal input (BS) 470Ω Remote ON/OFF (+) 560Ω 2.4V Remote ON/OFF (-) BA75T/BA100T/BA100R...
If you do not want to start the connected devices, turn OFF their switches or set the auto startup setting after recovery from power failure (“Setting” switch 2) to ON (Auto startup is not performed). BA75T/BA100T/BA100R...
Turn OFF all power to the unit and connected devices, and reduce the number of connected continuously devices. Then, turn the power to the unit and connected devices back ON and check whether " " is displayed on the status indicator. See also “3-4 Interpreting beeps and displays”, BA75T/BA100T/BA100R...
9 References 9-1 Specifications 9 References 9-1 Specifications Model BA75T BA100T BA100R Full-time inverter supply method (Automatic Switching) Operation method Method Forced air cooling Cooling method 100/110/115/120 VAC Rated input voltage 70±2 to 146±2 V AC (with less than 90% connection load) Input voltage range 80±2 to 146±2 V AC (with 90% or more connection load)
(and the battery level lowers) to approximately 80% over half a year, and to approximately 50% over a year. Higher the storage temperature is, faster the battery will self-discharge. Storage temperature Auxiliary charging interval 40°C or less 2 months 30°C or less 4 months 25°C or less 6 months BA75T/BA100T/BA100R...
9 References 9-4 China RoHS Information 9-4 China RoHS Information BA75T/BA100T/BA100R...
Page 104
No part or whole of this manual may be reproduced without permission. The contents of this manual are subject to change without notice. Corporation K1L-D-14006A...