Uninterruptible Power Supply BN75R/BN150R/BN300R Instruction Manual 使用说明书 BN75R BN75R BN150R BN150R/BN300R • This manual provides important safety-related information. Thoroughly read and understand this manual before installing and using the product. • Keep this manual in a convenient location so that you can refer to it whenever necessary.
10ms, and sine wave output is continued. ● Output capacity is 750VA/680W for BN75R, 1.5kVA/1350W for BN150R, 3kVA/2700W for BN300R. Notes on the use of the Backup Power Supply This product is designed and manufactured for use with FA or OA equipment such as per- ●...
This symbol indicates earth ground. This symbol indicates turning on/off UPS. 3. INTERNAL BATTERY Internal battery voltage is 24VDC for BN75R. 48VDC for BN150R and 72VDC for BN300R. 4. TEMPERATURE RATING The maximum ambient temperature of the UPS is 40 °C .
Procedure from installation to operation Read “Safety precautions” Start Page v Remove the product from the package and check the contents Page 1 Installation/connection Perform installation and connection Page 5 Are you Read “Using the UPS using UPS monitoring monitoring software and software or contact contact signal”...
Table of Contents Table of Contents Introduction ............................i IMPORTANT SAFETY INSTRUCTION ....................ii Safety precautions ..........................v 1. Preparation .............................1 1-1 Unpacking the product ........................1 1-2 Checking the contents ......................... 1 1-3 Name of each part ..........................2 1-4 Explanation of symbols used on unit....................
● Dropping or toppling the unit may cause injury. ● The approximate weights of the units are 13.5kg (BN75R), 21.5kg (BN150R) and 32kg (BN300R). ● If you drop the unit, stop using it and have it inspected and repaired. For repair, contact us; ____ Do not hold the side of the front panel when lifting.
Page 7
● Overcurrent may damage the UPS. Connect the unit to a wall outlet (commercial power) with the appropriate capacity (12A or greater for BN75R, 20A or greater for BN150R and 40A or greater for BN300R.). ● Otherwise, the power cord may be heated.
Page 8
Caution (for installation and connection) Do not pinch or sharply bend the cable. Do not fold or knot the cable. ● Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire. ● If the cable is damaged, stop using the unit and have the cable repaired. ● For repair, contact us; ____ All of the included accessories are designed to be used exclusively with the unit.
Page 9
Safety precautions Caution (for use) Do not allow the unit to come in contact with water. If you drop the unit, stop using it. ● Doing so may cause an electric shock or a fire. ● If the unit becomes wet or is dropped, immediately stop using it, disconnect the AC input plug from the wall outlet (commercial power) and have it inspected and repaired.
Page 10
Not doing so could cause injury or burns due to liquid (acid) leakage. Use a specified battery for replacement. ● Not doing so may cause a fire. ● Replacement battery pack for BN75R: BNB75R BN150R: BNB150R BN300R: BNB300R Do not replace the battery in a place where there is flammable gas. ● Spark may occur when connecting the battery, which may cause an explosion or fire.
Page 11
● The input surge protection GND screw is the gray screw on the right side (for the BN75R) or left side (for the BN150R and BN300R). Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
Page 12
Notes Check system operation beforehand if the unit is used in combination with a device whose power supply voltage and frequency fluctuate widely, such as a generator. ● If the generator’s output voltage/frequency falls out of the input voltage/frequency range, the unit will enter Battery Mode.
Open the package box and take out the UPS and accessories. Checking the contents Check whether all the package contents are included and there is no damage found on their appearance. If you should notice defects or anything wrong, contact us; OMRON Electronic Systems & Equipments Customer Support Center. BN75R...
This section describes the name of each part of the UPS. For information on the function of each part, refer to "2. Installation and connection" on page 5 and "3. Operation" on page 24 that provides the details. Front view <BN75R> <Air vent> <Operation panel> BN75R <BN150R/BN300R>...
.Preparation Rear view <BN75R> <BN150R> <BN300R> A. AC Input cable G. Option slot B. AC Input overcurrent protection switch H. Power supply output receptacle A C. Grounding terminal (M4 screw) I. Power supply output receptacle B D. RS-232C port J. Power supply output receptacle C E. USB port K. Cooling fan F. Remote ON/OFF port...
R/BN R/BN Explanation of symbols used on unit Symbol Description Start the UPS. Stop the UPS. UPS output power enabled, supplied by operating on line mode, battery mode. UPS output power enabled, supplied by operating on battery mode. Batteries at end of useful life, necessary to replace the batteries.
Dropping or toppling the unit may cause injury. ● ● The approximate weights of the units are units are 13.5kg (BN75R), 21.5kg (BN150R) and 32kg (BN300R). ● If you drop the unit, stop using it and have it inspected and repaired.
Page 18
R/BN R/BN Caution (for installation and connection) Do not disassemble, repair, or modify the unit. ● Doing so may cause an electric shock or a fire. Do not install the unit in other than specified orientations. ● Dropping or toppling the unit may cause injury. ● If you install the unit in an orientation other than specified, the unit cannot be protected from a battery fluid leakage. ● Use the included vertical stand when positioning the unit vertically.
● The input surge protection GND screw is the gray screw on the right side (for the BN75R) or left side (for the BN150R and BN300R). Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
Page 20
R/BN R/BN Notes If this unit is used for an inductive device such as a coil or motor, check the operation beforehand. ● With some types of devices, the effect of inrush current may cause this unit to stop operating properly. Check system operation beforehand if the unit is used in combination with a device whose power supply voltage and frequency fluctuate widely, such as a generator.
.Installation and connection Installation The UPS permits the following installing methods. Choose the one best suited for the environment. 2-2-1. Rackmount installation 2-2-2. Stationary installation Horizontal ● Upright intatllation (Only BN150R and BN300R) ● Do not use this unit in any position other than the “correct positions” indicated in the illustration below. Note Before installing this device, make a record of the serial number of this device.
Page 22
Without the support angles, the front clamp alone cannot support the weight of the UPS. ● The mass of each unit: BN75R: Approx. 13.5kg BN150R: Approx. 21.5kg BN300R: Approx. 32kg In a case where the UPS is to be mounted on a rack, place it on the lower part of the rack.
Page 23
.Installation and connection (2) Use the 4 included ear mounting flat-head screws (2 sets of 2 screws) to securely fasten the ears to the left and right sides of the UPS. ② ② ② The support angles cannot be attached to special EIA racks. (3) Place the UPS on the rack rails and push it completely into the rack ③ , and use the 2 included EIA rack washers and EIA rack fixing screws (M5) to securely fasten the ears to the server rack.
Page 24
R/BN R/BN <BN150R/BN300R> Items included in the 19-inch rack support angle mounting bracket set ● Rack rail (front) L ......1 Rack rail (front) R ......1 Rack rail (rear) ........ 2 Ears ..........2 Rail length fixing screws (M4) ..6 Ear screws (M4) ......
Page 25
.Installation and connection (4) Use the 8 included ear mounting flat-head screws (2 sets of 4 screws) to securely fasten the ears to the left and right sides of the UPS. ④ ⑤ ⑤ The support angles cannot be attached to special EIA/JIS racks. (5) Place the UPS on the rack rails and push it completely into the rack ⑤ , and attach the 2 included ear fixing nuts to the rack aligning them with the hole positions on the ears. ⑥...
Page 26
Attach the included rubber feet for horizontal installation to the specified locations on the bottom of the product. For stationary horizontal installation, make sure that this product does not slide or fall. BN75R BN150R ● U pright installation (Only BN150R and BN300R) Use the upright stands (2) included with the product. If the upright stands are not used, the UPS may fall over due to vibration or other reason.
.Installation and connection Connecting the equipment Caution Do not connect devices with rated voltage of 100 VAC or higher. ● The rated output voltage of this device is 100 VAC. ● Overcurrent may damage the connected devices. Connecting a device to the power supply output ●...
Page 28
External HDD Modem or other External HDD peripheral peripheral BN150R BN75R Modem or other External HDD peripheral BN300R • When using a 2-pin input plug with a grounding wire, connect the grounding wire to earth in building. When using a 2-pin input plug with a grounding wire, connect the grounding wire to earth in building.
(commercial power) with rated input voltage (100V to 120V AC). ● Connecting to a wall outlet (commercial power) of a different rated voltage may result in fire. ● The unit may fail. The BN75R AC input plug cannot be changed. ● The AC input plug for the BN150R and BN300R can be changed according to the operating ● environment.
Page 30
R/BN R/BN 2-4-1. Connecting the AC input plug BN75R connection procedure ● Provide a wall outlet (commercial power) suitable for the shape of the 15A plug (NEMA 5-15R). ● It is possible to connect to a 2-pin outlet using the included 3P-2P adapter.
Page 31
.Installation and connection 2-4-2. Connecting to BN300R input terminal block Caution When connecting the AC input directly from a power switchboard to the BN300R, make sure that the wiring work is performed by a qualified electrical engineer (with Type II certification or higher). To use the BN300R with up to 3000VA/2700W, a wiring capacity of 42A or more is ●...
Page 32
R/BN R/BN Connectable wire size 5.0 to 8.0mm Amount of stripped wire 5.5mm Tightening torque 1.355Nm (12 lb-in) Recommended cable size 8mm (AWG8) Securely fasten the screws with a tightening ● Screw torque of 1.355Nm (12 lb-in) or more. (5) Fix the AC input terminal block cover to the console by screws. (6) After connecting to commercial power, turn ON the INPUT PROTECTION switch (input overcurrent protection switch) on the back of the unit.
.Installation and connection Checking the operation When you finish connecting the unit, confirm that the backup operation works properly. Check that the Battery Mode is performed normally according to the following procedure. (In this operation check, the effects of a power failure are reproduced by disconnecting the AC input plug from the wall outlet (commercial power).) (1) Press and hold the unit’s power switch for 2 seconds or longer to turn ON the power.
Page 34
R/BN R/BN (5) In Battery Mode, check the unit's LED display and beep sound. Does the status indicator appear as one of those shown below? Status indicator Beep Output Description Intermittent Backup is operating due to power failure or AC input error. Output will 4-second stop if Battery Mode continues.
.Installation and connection Charging the battery The battery automatically starts charging when the AC input plug is connected to a wall outlet (commercial power). (This occurs regardless of whether the power switch is ON or OFF.) The charging takes 4 hours to complete. ●...
Operation Precautions and notes for operation Take notice of following items during operation. Caution (for use) Do not allow the unit to come in contact with water. Do not drop the unit. ● Doing so may cause an electric shock or a fire. ● If the unit becomes wet, immediately stop using it, disconnect the AC input cable from the wall outlet (commercial power).
Page 37
.Operation Notes Before stopping the commercial power to the unit, turn OFF the power switch of the unit. ● The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery Mode, the battery life may be significantly shortened. Take measures for handling unforeseen accidents, such as data backup and system redundancy.
R/BN R/BN Start and stop procedures and basic operation The UPS status indicators and UPS setting change menu are displayed on the control display panel on the front of the unit. UPS status indicators (status screen) ● Status indicator Upper text Load level Output receptacle status indicator...
Page 39
.Operation When the unit is connected to a commercial power source with the power ● switch OFF and commercial power is supplied to it • The status indicator displays " ". • Power output is stopped. • The battery automatically starts recharging. •...
R/BN R/BN Operation during recovery from a power failure ● • The unit automatically resumes output via commercial power if it recovers from a pow er failure/input power supply error while it is providing power supply output. The spent battery starts charging.
Page 41
AC input plug setting.) “2-4 Connecting the AC input” → Page 17 See also [Example] • BN75R: Displays 750VA/680W as 100% • BN150R: Displays 1500VA/1350W as 100% (when the AC input plug setting is "20A" and the voltage sensitivity setting is "Standard") • BN300R: Displays 3000VA/2700W as 100% (when the AC input plug setting is "Hard wire")
UPS functions Suspending a beep When the beep is sounding, you can suspend it by pressing and holding the ESC switch for 0.5 seconds or longer. Self-diagnosis test This test performs a failure diagnosis on the unit and performs a test to check for battery deterioration. Use the procedure below to check whether a circuit failure has occurred inside the unit and whether battery replacement is required.
. UPS functions Battery life counter function This function notifies you with LED display and beep sound when the battery needs to be replaced. The battery life counter operates while commercial power is supplied after shipment. (When the ambi- ent temperature of the battery is higher than 25°C, the value of the counter will be incremented at a faster pace.) When the battery needs to be replaced, the battery replacement lamp will light up and beep will sound.
Page 44
R/BN R/BN Menu Description Setting Local Setting Language Set the language to be displayed on the LCD. LCD Setting Change the contrast of the LCD. LCD Auto off Set the amount of time after which the LCD turns off automatically. LCD Test Check that the LCD and LEDs light up.
Page 45
. UPS functions Menu Description BSsignal ValidRange ☆ Setting Dry Contact Set the status for receiving the BS signal. BSsignal Delay Time Set the delay time for the BS signal. BUsignal Delay Time Set the delay time for the BU signal. Dry Contact Logic Set the logic of each contact signal.
Measuring the backup time How to measure backup time The backup time you measure for the first time after purchase is the “initial value of the backup time.” You can precisely judge the deterioration condition of the battery if you measure the “initial value of the backup time” in advance at the time of a battery check. (1) Connect the AC input plug to commercial power and charge the battery for 4 hours (Charging time is extended 24 hours per unit, if additional battery unit is connected).
Page 47
. Measuring the backup time Backup time (25°C, initial value) BN300R BN150R BN75R 1000 1500 2000 2500 3000 Connection capacity (W) Backup time table Time unit: (Minutes) BN75R Connection capacity (W) Backup time 15.5 10.5 (Minutes) BN150R Connection 800 1000 1200 1350...
Maintenance and Inspection Caution (for maintenance) When maintaining the connected equipment, turn OFF the unit’s power switch to stop the output, and stop the supply of commercial power. ● Even if commercial power to the UPS is stopped while it is in operation, the power output of this unit does not stop and power is supplied from the receptacle.
Not doing so could cause injury or burns due to liquid (acid) leakage. Use a specified battery for replacement. ● Not doing so may cause a fire. ● Replacement battery pack for BN75R: BNB75R BN150R: BNB150R BN300R: BNB300R Do not replace the battery in a place where there is flammable gas. ● Spark may occur when connecting the battery, which may cause an explosion or fire.
Page 50
(for the BN150R and BN300R) of the front panel of the unit. ① For the BN75R, pull the left side of the front panel towards you to remove it. ② a For the BN150R and BN300R, pull the right side of the front panel towards you to remove it. Be careful not to pull the cables of the LCD or disconnect the connectors.
Page 51
. Maintenance and Inspection <BN75R> Pull the battery connectors apart. ① Remove (turn counter-clockwise) the 2 screws that hold the battery cover in place. ② Slide the battery cover to the left and pull it towards your right side to remove it. ③...
Page 52
Remove the battery pack by holding the white label on the bottom of the battery pack (for the BN75R) or by holding the battery pack handle (for the BN150R and BN300R). Caution: Do not hold the connector or cable of the battery pack.
Page 53
You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this sound is not abnormal. Attach the front panel. Insert the front panel from the left side (for the BN75R) or right side (for the BN150R and BN300R), and fix it with the 2 screws. Battery replacement is complete.
R/BN R/BN Cleaning 1. Cleaning the UPS Moisten a soft cloth with water or detergent, squeeze it tightly, and wipe the product lightly. Do not use chemicals such as thinner and benzene. (They cause deformation or discoloration.) 2. Removing dust from the AC input plug, power supply output receptacles of the UPS Stop all the connected devices and the UPS and disconnect the AC input plug from a wall outlet (commercial power).
PowerAct Pro 4.x (Slave Agent) (Note1) SC20G → See 8-1 Note 1: The most recent version can be downloaded from our homepage (http://www.omron.co.jp/ese/ups/download/category_u.htm). Note 2: Files cannot be automatically saved. Note 3: The UPS automatically stops once the battery is depleted.
Page 56
R/BN R/BN • UPS monitoring software function list ● Supported ▲ Limited ━ Unsupported Network SNMP management management General applications applications applications Software title (Simple functions, standalone) (Advanced functions, (Advanced functions, network support) network support) Function Simple UPS service OS standard SNMP/Web Shutdown PowerAct Pro 4.x...
For more information, refer to the manual in the CD-ROM. 1. Connect the UPS to a computer. Cable: Included connection cable (RS-232C or USB) * The RS232C and USB cannot be used at the same time. <RS-232C> BN75R BN150R RS-232C端子 RS-232C端子 Connect to Connect to に接続する...
Page 58
R/BN R/BN <USB> BN75R BN150R RS-232C端子 RS-232C端子 Connect to Connect to に接続する に接続する USB port USB port コネ クタ Connect to コネ クタ Connect to USB port USB port port port Connector Connector Connector Connector Included connection cable (USB) Included connection cable (USB) BN300R RS-232C端子...
Page 59
. Using the UPS monitoring software and contact signal Explanation Scheduled operation using the UPS monitoring software ● When performing scheduled operation in which the UPS is stopped and a device such as a breaker is used to stop the UPS at the same time that commercial power stops, specify a period of no more than 3 months for the start of the next operation.
R/BN R/BN When performing auto-save functions using the UPS service in Windows Server 2003/XP + UPS service driver When using the included "UPS service driver", the OS standard UPS service in Windows Server 2003/ XP can be used. When there is a power failure the computer can be shut down. 1.
. Using the UPS monitoring software and contact signal Contact signal An additional contact signal card can be installed in the contact signal input/output slot on the back of the UPS. Contact signal card (model number: SC07), sold separately Contact Signal You can develop your unique system based on the following specifications to automate the pro- cess at a power failure.
Page 62
R/BN R/BN ● Remote ON/OFF Signal External contact Operate Open Start Remote ON/OFF signals can be used to start and stop the UPS, by using either an externally Close Stop connected contact or the ON/OFF status of the open collector circuit. To use this function, turn on the Power Switch of the UPS.
Page 63
● Insert method of contact signal card (1) Remove the two screws below the signal card expansion slot on the back of the unit, and re- move the cover. <BN75R> <BN150R> <BN300R> (2) Carefully insert the contact signal card whose settings have been changed, and securely tighten the 2 screws.
Page 64
R/BN R/BN 7-4-5. Remote ON/OFF port Pin assignment Pin number Signal name Remote ON/OFF (+) Remote ON/OFF (-) Front view Screw size: Inch screw #4-40 UNC 7-4-6. Contact Signal ratings ● Signal output (BL, TR, BU, WB, NBU) ● UPS Stop Signal input (BS) Photo coupler ratings Input voltage HIGH(ON) 5 to 12 VDC...
Page 65
A relay output type contact signal card is available for separate purchase. It can be loaded into the option slot on the back of the UPS. Visit our website for more details. (URL: http://www.omron.co.jp/ese/) • Contact signal card (relay output type) ..... Model number: SC08 (sold separately)
An SNMP/Web card can be loaded into the option slot on the back of the unit. • SNMP/Web card (model number: SC20G), sold separately (1) Remove the 2 screws, and remove the cover. <BN75R> <BN150R> <BN300R> (2) Carefully insert the SNMP/Web card (model number: SC20G), and securely tighten the 2 screws.
Number of controllable computers 32 max. (including slave UPS when coordinated shutdown is enabled) UPSMIB (RFC1628) Support MIB OMRON MIB 0 to 40°C/25 to 85% Operating temperature/humidity * Note that the range of the operating temperature/humidity differs from that of BN-R.
1. Make sure the AC input is securely connected to commercial power. The LCD does not appear when 2. AC input overcurrent protection is activated and power is cut. (For BN75R the AC input plug is connected and BN150R, the black button has popped up. For BN300R, it is tilted to- to commercial power and the wards OFF.)
References A. Specifications Model BN75R BN150R BN300R Method Operation method Line-interactive method Cooling method Forced air cooling Input Rated input voltage 100 VAC Input Sensitivity setting: Standard 89±3 to 118V±3 VAC voltage Sensitivity setting: Low 84±3 to 118V±3 VAC range Sensitivity setting: High 89±3 to 113V±3 VAC...
Charger Output group B DC-DC converter Battery Output group C Line mode Battery mode Bypass mode D. Related products Description BN75R BN150R BN300R Replacement battery pack BNB75R BNB150R BNB300R SNMP/Web card SC20G SC20G SC20G Connection cable for Windows UPS service...
Page 85