Omron BN75R Instruction Manual page 41

Table of Contents

Advertisement

3
.Operation
No.
Icon
8
9
10
11
12
Load/battery level meter
The load level meter displays the power consumption of the connected devices as a percentage.
The maximum connection capacity is displayed as 100%. (The maximum connection capacity var-
ies depending on the AC input plug setting.)
"2-4 Connecting the AC input" → Page 17
See also
[Example]
• BN75R: Displays 750VA/680W as 100%
• BN150R: Displays 1500VA/1350W as 100%
(when the AC input plug setting is "20A" and the voltage sensitivity setting is "Standard")
• BN300R: Displays 3000VA/2700W as 100%
(when the AC input plug setting is "Hard wire")
The battery level meter displays the remaining battery level as a percentage.
29
Mode
Beep
Battery
Intermittent
mode
4-second
Battery low
Intermittent
1-second
Battery
None
empty
Battery not
Intermittent
connected
2-second
Battery
Intermittent
weak
2-second
intervals
Over load
Intermittent
0.5-second
intervals
UPS error
Continuous
Discription
Backup is operating due to power
failure or AC input error
Battery level is low, so output will
stop soon.
Battery is dead, so output
stopped
Battery is not connected
The self-diagnostic test
determined that the battery was
deteriorated, or the battery life
counter went off-scale
There are too many connected
devices and the rated capacity is
exceeded
There is the internal error
Solution
Shut down the connected
devices to stop them.
Charge the battery.
Connect the battery.
Replace the battery
You can replace the weak battery
with a separately purchased
replacement battery as needed
Reduce the number of connected
devices until the display appears
as in status No.2
Check the displayed message