References; Specifications - Omron BU150R Instruction Manual

Table of Contents

Advertisement

10 References

10-1 Specifications

Operation method
Method
Cooling method
Rated input voltage
Input voltage range
Frequency
Input
Input Maximum current *1
Phase
Input protection
Input plug shape
Rated output capacity
Commercial
Voltage
Operation and
Backup operation
Frequency
Commercial operation Sine wave
Output
Wavef
Backup operation
orm
Distortion rate
Phase
Output receptacle
Type
Voltage / Capacity x Quantity
Backup time
(25°C, initial characteristics)
Battery
Charging time
Battery
Expected life: 5
life
years
BU150R
Full-time inverter supply method (Automatic Switching)
Forced air cooling
AC100V/110V/115V/120V
AC70V±2V~146V±2V (with less than 90% connection
load)
50/60Hz±5.5Hz
15A
Single-phase, two-wire (grounded)
Non Fuse Breaker (20A)
NEMA 5-15P (*4)
1500VA/1200W (*4)
100V mode: 100VAC±2%, 110V mode: 110VAC±2%
115V mode: 115VAC±2%, 120V mode: 120VAC±2%
Commercial operation: Synchronized with input frequency
Backup operation: 50/60Hz±0.5%
Sine wave
6% max. (Rectified load, at rated output)
3% max. (Resistance load, at rated output)
Single-phase, two-wire (grounded)
NEMA 5-15R x 6
Sealed lead battery
12V/9Ah×4
10min. (900W)
6min. (1200W)
8 hours
Expected life: 5 years
10 References
10-1 Specifications
10
99

Advertisement

Table of Contents
loading

Table of Contents