Product Specifications
9.2.2 UPS Output
UPS Output Capacity
Output Voltage Regulation
Nominal Output Voltage
Output Voltage Harmonic Content
Output Current
Output Voltage Balance
Output Voltage Phase
Displacement
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Load Compatibility
Overload Capability
9.2.3 UPS Environmental
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMC
9-2
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
100% rated current
± 1% (10% to 100% load)
380 Vac, 400 Vac and 415 Vac nominal
2% maximum THD (linear load)
5% maximum THD (nonlinear load)
See Table 3-5.
< 2% for 100% maximum load imbalance (linear load)
< 2.5° for 100% maximum load imbalance (linear load)
0.1 Hz free running
± 4 Hz (default setting)
3 Hz per second (default setting)
0.9 pF Leading
0.7 pF Lagging
125% for 10 minutes
150 % for 1 minutes
150% for 150 milliseconds
0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Maximum 1000m (3300 ft) at 30°C without derating
-15 to +55°C, excluding batteries (prolonged storage above 40°C causes
rapid battery self-discharge)
5% to 95% maximum noncondensing
Less than or equal to 65 dB (80-120kVA) and 70dB (160-200kVA) at a 1m
distance, per ISO 7779
Meets IEC 62040-2 C3