Route the wiring to the terminal block:
a.
Interface cables can enter the UPS via right side panel or a knockout in the top (front/right corner) of
the cabinet. Remove the knockout from either of the two entry points.
b.
Route the wiring (see Figure 4-12) until the wire clears the shelf.
c.
Route the wire along the shelf under the interface housing to the wiring access (see Figure 4-12).
d.
Reinstall the cover using the retained hardware.
4.
Connect the building alarm interface wiring as shown in Table 4-1 and Figure 4-11.
5.
Reinstall the interface terminal cover using the retained hardware.
6.
If wiring parallel connections, proceed to paragraph 4.5.2; if wiring Mini-Slot connections, proceed to
paragraph 4.5.3;
7 .
Install the power terminal cover right and left sides using the provided hardware.
4-10
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
NOTE
Conduit and wiring enter from the central of the conduit landing plate.