Ups Input; Ups Output; Table 9-3. Ups Input Rating; Table 9-4. Ups Output Rating - Eaton 93E MK2 Installation And Operation Manual

Ups 10-40 kva 380/400/415v
Table of Contents

Advertisement

Product Specifications

9.2.2 UPS Input

Table 9-3. UPS Input Rating

Operating Input Voltage
Input Voltage Range
Operating Input Frequency Range
Input Frequency Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Battery Voltage
Battery Charging Capacity (432 Vdc)

9.2.3 UPS Output

Table 9-4. UPS Output Rating

UPS Output Capacity
Output Voltage Regulation
Nominal Output Voltage
Output Voltage Harmonic Content
Output Current
Output Voltage Balance
Output Voltage Phase Displacement < 2.5° for 100% maximum load imbalance (linear load)
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Load Compatibility
Overload Capability
82
380/400/415 Vac
190/330–276/478V (-15%, +20%) at 100% load
116/201-276/478V (-50%, +20%) at 50% load
50/60 Hz
40-72Hz
See Table 3-5.
Adjustable
5% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
432 Vdc Internal
5.3A maximum at any load up to100% load for 10 kVA UPS
5.3A maximum at any load up to100% load for 15 kVA UPS
5.3 A maximum at any load up to100% load for 20 kVA UPS
8A maximum at any load up to100% load for 30 kVA UPS
10.6A maximum at any load up to100% load for 40 kVA UPS
100% rated current
± 1% (10% to 100% load)
380 Vac, 400 Vac and 415 Vac nominal
2% maximum THD (linear load)
5% maximum THD (nonlinear load)
See Table 3-5.
< 2% for 100% maximum load imbalance (linear load)
0.1 Hz free running
± 4 Hz (default setting)
3 Hz per second (default setting)
0.9 PF Leading
0.7 PF Lagging
≦ 110% for 60
minutes
≦ 125% for 10
minutes
≦ 150 % for 1 minutes
≧ 150% for 500 milliseconds
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation