Table 3-5.Input/Output Ratings And External Wiring Requirements For The Eaton 9E 80-200Kva - Eaton 9E Installation And Operation Manual

80–200 kva (380/400/415v)
Hide thumbs Also See for 9E:
Table of Contents

Advertisement

UPS Installation Plan and Unpacking

Table 3-5.Input/Output Ratings and External Wiring Requirements for the Eaton 9E 80-200kVA

Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.99 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Neutral, (1) Ground
Conductor Size (Phase A, B, C and N)
Conductor Size (Ground)
AC Input to UPS Bypass (Five Wire, Dual-Feed)
Full Load Current
(3) Phases, (1) Neutral
Conductor Size (Phase A, B, C )
Conductor Size (N)
DC Input from External Battery
(1) Positive, (1) Negative
Conductor Size
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral
Conductor Size (Phase A, B,C )
Conductor Size (N)
Neutral (N) (Mains/Load):( Non-linear lad )
Backfeed protection device
NOTE
Callout letters
3-8
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
cross-
sections
min
max
min
max
min
max
min
max
min
max
min
max
min
max
A
B
C
D
,
,
, and
map to Figure 5-5.
Units
80
100
kVA
72
90
kW
Volts
400/400
400/400
Amps
124
154
mm
25
35
2
mm
95
95
2
mm
25
35
2
mm
95
95
2
Amps
130
162
mm
35
35
2
mm
95
95
2
mm
35
35
2
mm
95
95
2
Total Amps
167
206
mm
35
50
2
mm
120
120
2
Amps
104
130
mm
25
35
2
mm
95
95
2
mm
25
35
2
mm
95
95
2
1.7times
Clearance distance:> =2.0mm
Break time < =15s
Rating 50/60 Hz
120
160
200
108
144
180
400/400
400/400
400/400
187
248
309
50
70
95
120
240
240
50
70
95
120
240
240
196
261
326
50
95
185
120
240
240
50
95
185
120
240
240
250
333
412
70
185
300
150
400
400
157
208
261
35
50
70
95
150
150
35
50
70
95
150
150