Eaton 9E Installation And Operation Manual

Eaton 9E Installation And Operation Manual

80–200 kva (380/400/415v)
Hide thumbs Also See for 9E:
Table of Contents

Advertisement

®
Eaton
9E UPS
80–200 kVA (380/400/415V)
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 9E

  • Page 1 ® Eaton 9E UPS 80–200 kVA (380/400/415V) Installation and Operation Manual...
  • Page 3 National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ©Copyright 2012 Eaton Corporation, BAOAN, SZ, CHINA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 5: Table Of Contents

    Completing the Installation Checklist ............4-17 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 6 6.4.11 Using the Remote Emergency Power-off Switch ......... 6-23 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 7 UPS Environmental ..............Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 8 Table of Contents This page intentionally left blank. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 9 Eaton 9E UPS (80–200 kVA) ........
  • Page 10 List of Figures This page intentionally left blank. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 11 UPS External Power Cable Terminations for the Eaton 9E 80-200kVA .......
  • Page 12 List of Tables This page intentionally left blank. viii Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 13: Introduction

    Chapter 1 Introduction protect the customer's load from power failures. The Eaton 9E 80-200 kVA online power protection system is used to prevent loss of valuable electronic The Eaton ® 9E 40–60 kVA uninterruptible power supply (UPS) is a true online, continuous-duty,...
  • Page 14: Ups Standard Features

    The 9E Series UPS offers a High-Efficiency (HE) normal mode with double-conversion on demand that allows the UPS to operate in standby bypass mode. This mode allows the 9E UPS to achieve 98% efficiency while still protecting the load. See Chapter 6, “UPS Operating Instructions, ” for additional information.on setting the UPS to work in High Efficiency mode.
  • Page 15: Parallel System

    Remote Emergency Power-off (REPO) control or Mini-Slot communication cards. Using This Manual This manual describes how to install and operate the Eaton 9E 80-200 kVA. Read and understand the procedures described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 6.3.13).
  • Page 16: Conventions Used In This Manual

    • Installation instructions, including site preparation, planning for installation, wiring and safety information, and detailed illustrations of cabinets with dimensional and connection point drawings Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain copies of these manuals.
  • Page 17: Getting Help

    • Regional locations and telephone numbers • A question about any of the information in this manual • A question this manual does not answer Please call your local service representative. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 18 Introduction This page intentionally left blank. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 19: Safety Warnings

    UPS and battery systems, and required precautions. Keep unauthorised personnel away from equipment. Consider all warnings, cautions, and notes before installing or servicing equipment. DO NOT DISCONNECT the batteries while the UPS is in Battery mode. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 20 This product is designed for commercial and industrial applications. In a residential environment, the product may cause radio interference , in which the user may be required to take additional measures. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 21: Section 1-Installation

    Section 1 Installation...
  • Page 23: Ups Installation Plan And Unpacking

    If the UPS is to be operated at an altitude higher than 1000m (3300 ft), contact an Eaton service representative for important information about high altitude operation. The operating environment must meet the weight, clearance, and environmental requirements specified.
  • Page 24: Table 3-1. Ups Cabinet Weights

    • Ambient Temperature Range: 0–40°C (32–104°F) • Recommended Operating Range: 20–25°C (68–77°F) • Maximum Relative Humidity: 95%, noncondensing Table 3-3. 9E Required Clearance A : 9E Required Clearance for paralleled adjacent UPS or UPS and adjacent PDU 80kVA 100kVA 120kVA...
  • Page 25: Figure 3-1. Ups Cabinet Dimensions (Front And Right Side Views)

    UPS Installation Plan and Unpacking 9E 80-120 kVA 9E 160-200 kVA Figure 3-1. UPS Cabinet Dimensions (Front and Right Side Views) Dimensions are in millimetres [inches] Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 26: Figure 3-2. Ups Cabinet Dimensions (Top And Bottom Views)

    UPS Installation Plan and Unpacking 9E 80-100 kVA 9E 120 kVA 9E 160-200 kVA Figure 3-2. UPS Cabinet Dimensions (Top and Bottom Views) Dimensions are in millimetres [inches] Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 27 UPS Installation Plan and Unpacking 9E 80-120 kVA 9E 160-200 kVA Figure 3-3. UPS Cabinet Centre of Gravity Dimensions are in millimetres [inches] Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 28: Ups System Power Wiring Preparation

    TERMINALS INCLUDING THE PROTECTIVE EARTH RISK OF VOLTAGE BACKFEED 自 动反 向 馈 电危险 ! 线路 施 工前, 请断 开UPS, 确 保 所有 端 子 之间包括 保 护地没 有危险 电压 。 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 29: Table 3-6. Ups External Power Cable Terminations For The Eaton 9E 80-200Kva

    • When single-phase current exceeds 100A, switches of protective atmosphere should be equipped with arc-control device. Figure 4-6 and Figure 4-7 show the location of the UPS power cable terminals. Table 3-6. UPS External Power Cable Terminations for the Eaton 9E 80-200 kVA Tightening Torque Maximum Size of Pressure Termination...
  • Page 30: Table 3-5.Input/Output Ratings And External Wiring Requirements For The Eaton 9E 80-200Kva

    UPS Installation Plan and Unpacking Table 3-5.Input/Output Ratings and External Wiring Requirements for the Eaton 9E 80-200kVA Units Rating 50/60 Hz cross- Basic Unit Rating sections Input and Output Voltage Volts 400/400 400/400 400/400 400/400 400/400 AC Input to UPS Rectifier (0.99 Minimum pF)
  • Page 31: Table 3-7. Recommended Input Circuit Breaker Ratings

    100% Rating 261A There is no manual DC disconnect device within the UPS. Battery voltage is computed at 2 volts per cell . Rated battery current is computed at 2 volts per cell. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 32: Ups System Interface Wiring Preparation

    • All interface wiring and conduit is to be supplied by the customer. • When installing external interface wiring between a REPO or building alarm and the UPS interface terminals, conduit must be installed between each device and the UPS cabinet. 3-10 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 33: Inspecting And Unpacking The Ups Cabinets

    Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for removing the cabinet from the pallet. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 3-11...
  • Page 34: Figure 3-4. Ups Cabinet As Shipped On Pallet (Wood Container Removed)

    Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
  • Page 35: Ups System Installation

    Attach the ramp extension to the front of the ramp by inserting the tabs on the extension into the slots at the bottom of the ramp. If the leveling feet are not fully retracted, turn the leveling feet until they are retracted. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 36: Figure 4-1. Removing The Front Shipping Bracket

    11. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to the front and rear of the UPS cabinet with the angle facing outward (see Figure 4-1 and Figure 4-3). 12. Secure the cabinet to the floor with customer-supplied hardware. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 37: Figure 4-2. Attaching The Ramp To The Pallet

    Ramp (side panel from wood container) Figure 4-2. Attaching the Ramp to the Pallet Shipping Bracket Bolts Pallet Shipping Bracket Bolts Front Shipping Bracket Figure 4-3. Removing the Rear Shipping Bracket Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 38: External Battery Cabinet Installation

    The amount of gas given off is less than forflooded cells, but when planning the battery installation, allowance must be made foradequate ventilation and heat Eaton 9E UPS (40–60 kVA, 208/220V) Installation and Operation Manual P-164000058—Rev 2 dissipation. Valve regulated cells are not completelymaintenace- free. They must be kept clean and their connections checked periodicallyto ensure they are tight, and that there is no evidence of corrosion.
  • Page 39: External Power Wiring Installation

    AC input idle-run. • Protective earthing terminals on the UPS for mains supply and load supply use only. The earth protection of battery cabinet must be connected individually, no relation to UPS. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 40: Figure 4-6. Power Terminal Locations

    DC Input from External Battery + DC Input from External Battery - DC Input from External Battery - RIGHT VIEW 80-120kVA Standard FRONT VIEW Figure 4-6. Power Terminal Locations 80-120kVA Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 41: Figure 4-7 . Power Terminal Detail

    Phase C (L3) Phase C(L3) AC Input to AC Input to UPS Bypass AC Input to UPS Bypass AC Input to UPS Rectifier UPS Rectifier Figure 4-7. Power Terminal Detail 160-200 kVA Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 42: Installing Interface Connections

    THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF EATON AND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON.
  • Page 43: Figure 4-10. Interface Terminal Detail (Terminal Cover Removed)

    THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUB BY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERE AND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON.
  • Page 44 If wiring parallel connections, proceed to paragraph 4.5.2; if wiring Mini-Slot connections, proceed to paragraph 4.5.3; Install the power terminal cover right and left sides using the provided hardware. 4-10 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 45: Figure 4-12. Interface Wiring Access

    9E 160-200 kVA F R O N T V I E W ( R E M O V E T H E MIDDLE COVER PLATE) Figure 4-12. Interface Wiring Access Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 4-11...
  • Page 46: Installing Parallel Pull Chain And Can Control Wiring And Connections

    Route the wiring (see Figure 4-12) to the wiring access (see Figure 4-12). Secure the wiring to the four mounting clips provided using Zip ties. Reinstall the wires to cover using the retained hardware. Install the power terminal cover up and down sides using the provided hardware. 4-12 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 47: Installing Mini-Slot Interface Connections

    NOTE LAN drop for connection to UPS communications card is to be supplied by customer. For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8) To install wiring: If not already installed, install the LAN drop.
  • Page 48: Figure 4-14. Parallel Ups Control Wiring

    Figure 4-14. Parallel UPS Control Wiring UPS 1 Bypass inputs to UPSs Battery UPS 2 Battery UPS 3 Outputs from UPSs Battery UPS 4 Battery Figure 4-15. Parallel UPS system connections 4-14 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 49: Installing A Repo Switch

    The REPO switch must be a normally-open or normally-closed latching-type switch not tied into any other circuits. NOTE 4 This procedure is intended for installing the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure, and Figure 4-17 and Figure 4-18 as a guide.
  • Page 50: Figure 4-17. Normally-Open Repo Switch Wiring

    Back of UPS Cabinet Wire Size Tightening Torque 3 NO Twisted Wires (2) 7 lb in 14-22 AWG (0.8 Nm) (0.75 -4.0 mm REPO TB REPRO Switch Twisted (No) Wires Figure 4-17. Normally-Open REPO Switch Wiring 4-16 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 51: Initial Startup

    Eaton Customer Service Engineer, or the warranty terms may become void.This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 52  Air conditioning equipment is installed and operating correctly.  The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a  level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.
  • Page 53 UPS System Installation Notes Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 4-19...
  • Page 54 UPS System Installation This page intentionally left blank. 4-20 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 55: Section 2-Operation

    Section 2 Operation...
  • Page 57: Understanding Ups Operation

    Understanding UPS Operation UPS System Overview The Eaton 9E UPS is a continuous-duty, solid-state, transformer-free, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load. The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server, and digital signal processor (DSP) logic.
  • Page 58: Single Ups

    5.2.1 Modes The Eaton 9E UPS supports a critical load in four different modes of operation: • In Standard Normal mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power. In this mode, the battery charger also provides charging current for the battery, if needed, Standard mode is the standard normal operating mode.
  • Page 59: High-Efficiency Mode

    HE mode , if selected, is a normal operating mode, and not an alarm condition. While the UPS is in this mode, the NORMAL light on the front display will illuminate. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 60: Bypass Mode

    Contactor Contactor Battery Converter Main Power Flow Battery Contactor Switch Contactor Trickle Current Closed Energised Open De-Energised Battery Figure 5-3. Path of Current Through the UPS in standard Bypass Mode Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 61: Battery Mode

    Normal mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms may be seen for a short time due to the current required to recharge the battery. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 62: Single Ups Unit System Oneline Configurations

    Voltage Oneline Drawing UPS Model Input Output System Type See Figure 5-5 9E-100/80 380/400/415 380/400/415 Single Reverse Transfer UPS with External Battery 9E-100/100 9E-120/120 9E-200/160 9E-200/200 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 63 Fuse (Optional 80-120 kVA) Output Switch Battery Converter Battery Contactor Fuse CABINET Battery Breaker EXTERNAL BATTERY CABINET NOTE Callout letters A,B,C,and Dmap to Table 3-5. Figure 5-5. UPS System Oneline Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 64: Understanding Ups Operation

    Understanding UPS Operation This page intentionally left blank. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 65: Ups Operating Instructions

    The controls and indicators identified and described in this section are used to control and monitor UPS operation. Figure 6-1 shows the controls and indicators and Figure 6-2 shows the UPS switches. Control Panel Control Panel Door Latch Door Latch Figure 6-1. UPS Controls and Indicators Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 66: Control Panel

    6.1.1 Control Panel The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 6.2. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 67: Using The Control Panel

    When the unit powers up, the screen displays the Eaton logo as shown in Figure 6-3. To advance to the Main When the unit powers up, the screen displays the Eaton logo as shown in Figure 6-3. To advance to the Main When the unit powers up, the screen displays the Eaton logo as shown in Figure 6-3.
  • Page 68: System Events

    This message is also written to the Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 69: Using The Lcd And Pushbuttons

    Figure 6-4. Parts of the LCD The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, UPS status, load percent, and battery runtime for the UPS. The top line of display blinks while scrolling when the system needs attention.
  • Page 70: Using The Menu

    The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Eaton Eaton 9E 9E 9E 9E Series Series UPS Eaton Eaton Series Series Figure 6-5. Main Menu and Mimic Screen Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 71: Display Menu Operation

    RETURN pushbutton to display the Set Date and Time screen. To return to the System Setup screen, press the ESC pushbutton. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 72 LEFT or RIGHT arrow pushbutton to select the password character position. Use the UP or DOWN arrow and then pushbutton to change the password character. Once the password is entered, select CHANGE press the RETURN pushbutton Controls See paragraph 6.2.7 for details. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 73: System Controls

    Table 6-4 describes the control functions and provides instructions to access and use the command menu screens. Table 6-5 lists the typical System Status Screen Messages that are displayed during UPS operation. For detailed information about using the System Controls, see paragraph 6.3. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 74: Figure 6-7. Typical System Control Screen

    Turns the battery charger on. Resting Turns the battery charger off. Table 6-5. Typical System Status Messages Function Message Load Off; Bypass; Online, HE Bypass Off; On; Available Charger Charger Resting; Charger 6-10 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 75: Single Ups Operation

    If the inverter output of the UPS is not available and the critical load needs to be energised: CAUTION In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 6-11...
  • Page 76: Transfer From Normal To Bypass Mode

    BYPASS command, then press the RETURN pushbutton. The UPS transfers to Bypass mode. The BYPASS status indicator is illuminated. The power module remains on. WARNING Power is present inside the UPS cabinet. 6-12 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 77: Transfer From Bypass To Normal Mode

    Loosen the screws that fix the cover over the Neutral switch and push the cover to the left, then open the Neutral switch. NOTE The Neutral Switch should remain closed unless operated by a service technician. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 6-13...
  • Page 78: Transfer From Internal Maintenance Bypass To Normal Mode (Optional On 80-120Kva)

    If the UPS contains a Bypass input switch, open the Bypass input switch. If the UPS contains a Maintenance Bypass switch, open the Maintenance Bypass switch. Open the UPS input and bypass feeder circuit breakers. Open all external battery breakers. 6-14 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 79: Charger Control

    All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this feature only when you want to de-energise the critical load. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 6-15...
  • Page 80: Using The Remote Emergency Power-Off Switch

    NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 81: Multiple Ups Parallel Operation

    Standard Normal mode. It takes approximately one minute for the UPS to achieve Standard Normal mode. The Normal status indicator is illuminated. 17 . If the UPS contains an output switch, close the output switch. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 6-17...
  • Page 82: Starting The Parallel Ups In Bypass Mode

    On the UPS System Control screen, select the NORMAL BYPASS command, then press the RETURN pushbutton. All of the UPSs transfer to Bypass mode. The BYPASS status indicator is illuminated. The power module remains on. 6-18 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 83: Transfer From Bypass To Normal Mode

    Open the UPS input and, if installed, the bypass feeder circuit breakers for the UPS being shut down. If EBCs are installed, open all battery breakers The UPS is now completely shut down. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 6-19...
  • Page 84: Single Ups Restart

    If the UPSs contain an output switch, open the output switch. Open all of the MOBs. Open all of the UPSs input and bypass feeder circuit breakers. 10. Open all external battery breakers 6-20 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 85: Charger Control

    Select the CONTROLS symbol on the main menu bar on the UPS to be tested. The System Control screen is displayed. Select Battery on the System Control screen. On the Battery System Control screen, select the RESTING TESTING command, then press the RETURN pushbutton. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual 6-21...
  • Page 86: Using The Ups Load Off Command

    To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph 6.4.1 or 6.4.2. WARNING Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are opened because of the installed external battery cabinet. 6-22 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 87: Using The Remote Emergency Power-Off Switch

    NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 88 UPS Operating Instructions This page intentionally left blank. 6-24 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 89: Communication

    This chapter describes the communication features of the Eaton 9E UPS. For terminal wiring information, see This chapter describes the communication features of the Eaton 9E UPS. For terminal wiring information, see paragraph 3.2.3 and paragraph 4.4. For location of the customer interface panel and terminals, see Figure 4-9 paragraph 3.2.3 and paragraph 4.11.
  • Page 90 Communication This page intentionally left blank. Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 91: Ups Maintenance

    Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF . VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service contact an Eaton service representative.
  • Page 92: Performing Preventative Maintenance

    Monitor system parameters as described in paragraph 6.2, “Using the Control Panel” . Check the UPS air filters (located behind the front door) and wash or replace as necessary. See Figure 8-1 for filter location. Contact an Eaton service representative for replacement filters. To remove the filters: CAUTION Verify washed filter is thoroughly dry before reinstalling.
  • Page 93: Annual Maintenance

    8.2.3 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorised service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 8.2.4 BATTERY Maintenance Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorised service personnel.
  • Page 94: Installing Batteries

    Maintenance Training A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Help Desk (see paragraph 1.8).
  • Page 95: Product Specifications

    40A maximum at any load up to100% load for 120KVA UPS 64A maximum at any load up to100% load for 160KVA UPS 80A maximum at any load up to100% load for 200KVA UPS Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 96: Ups Output

    5% to 95% maximum noncondensing Relative Humidity (operating and storage) Less than or equal to 65 dB (80-120kVA) and 70dB (160-200kVA) at a 1m Acoustical Noise distance, per ISO 7779 Meets IEC 62040-2 C3 Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual...
  • Page 98 614-00752-02...