Product Specifications; Model Numbers; Specifications; Ups Input - Eaton 9E Installation And Operation Manual

80–200 kva (380/400/415v)
Hide thumbs Also See for 9E:
Table of Contents

Advertisement

Chapter 9

Product Specifications

9.1 Model Numbers

The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Models
Eaton 9E-100/80
Eaton 9E-100/100
Eaton 9E-120/120
Eaton 9E-200/160
Eaton 9E-200/200

9.2 Specifications

The following sections detail the input, output, environmental, and battery specifications for the UPS.

9.2.1 UPS Input

Operating Input Voltage
Operating Input Frequency Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Battery Voltage
Battery Charging Capacity
Power Rating
80 kVA
100 kVA
120 kVA
160 kVA
200 kVA
380/400/415 Vac
50/60 Hz
See Table 3-5.
Adjustable
5% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
480 Vdc
32A maximum at any load up to100% load for 80KVA UPS
40A maximum at any load up to100% load for 100KVA UPS
40A maximum at any load up to100% load for 120KVA UPS
64A maximum at any load up to100% load for 160KVA UPS
80A maximum at any load up to100% load for 200KVA UPS
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
9-1