Multiple Ups Parallel Operation; Starting The Parallel Ups In Standard Normal Mode (Default Mode) - Eaton 9E Installation And Operation Manual

80–200 kva (380/400/415v)
Hide thumbs Also See for 9E:
Table of Contents

Advertisement

6.4

Multiple UPS Parallel Operation

The paragraphs in this section provide operating instructions for a UPS system containing multiple UPSs.
6.4.1

Starting the Parallel UPS in Standard Normal Mode (Default Mode)

To start the UPS system:
1.
Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (see Figure 6-1).
2.
Verify that all input breakers are open.
3.
If the UPSs contain a bypass breaker, verify that the bypass breakers are open.
4.
Close all Module Output Breakers (MOBs).
5.
Close all UPS input feeder circuit breakers.
6.
If the UPSs are wired for dual input, close all of the UPSs Bypass input feeder circuit breakers.
7 . Close all input breakers.
8. If the UPSs contain a bypass input switch, close all bypass input switches.
9. Close the door and secure the latch.
10. Close all external battery breakers.
11. Observe the UPS control panel display becoming active, indicating logic power.
12. Verify no alarms are active.
13. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
14. If not already selected, select UPS on the System Control screen.
15. On the UPS System Control screen, select the LOAD OFF
RETURN pushbutton.
16. If requested, enter the Level 1 password. Default password is 1111.
All rectifiers and inverters turn on. The inverters continue to ramp up to full voltage.
Once all inverters reach full voltage, the UPS output contactor closes and the static switch turns off. Power
is now supplied to the critical load in Standard Normal mode. It takes approximately one minute for the
UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.
17 . If the UPS contains an output switch, close the output switch.
NOTE 1
Refer to the External Battery Cabinet Installation Manual listed in paragraph 1.8 for EBC
battery breaker location.
NOTE 2
Start and control system wide function from UPS 1.
NORMAL command, then press the
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
UPS Operating Instructions
6-17