Table 3-6. Ups External Power Cable Terminations For The Eaton 9E 80-200Kva - Eaton 9E Installation And Operation Manual

80–200 kva (380/400/415v)
Hide thumbs Also See for 9E:
Table of Contents

Advertisement

• Refer to national and local electrical codes for acceptable external wiring practices.
• To allow for future kVA upgrades, consider installing a derated UPS using wiring and external overcurrent
protection breakers sized for a fully rated UPS.
• For external wiring, use 90°C copper wire. Wire sizes listed in Table 3-5 are for copper wiring only. If wire is
run in an ambient temperature greater than 30°C, higher temperature wire and/or larger size wire may be
necessary. Wire sizes are based on using the specified breakers.
• Material and labour for external wiring requirements are to be supplied by designated personnel.
• If installing an external maintenance bypass, all feeds to the UPS including the Rectifier Input Breaker (RIB) (if
installed) must have a service disconnect independent of the maintenance bypass power path. Most
maintenance bypass solutions provide UPS input feeds derived from but isolated from the maintenance
bypass power path. If the maintenance bypass solution being installed does not provide such functionality,
DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass.
• The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses four wires.
The phases must be symmetrical about ground (from a Wye/Star source) for proper equipment operation.
• Parallel UPS input wiring size requirements and output wiring size requirements from the UPSs to the Tie
Cabinet are the sames as those for single systems.
• This device is not equipped with its own mains separation device. It is , therefore, essential that the customer
install such a device at the installation site near the UPS.
• Install a proper three-pole overcurrent disconnect device before connecting to the UPS, the disconnect
device shall disconnect simultaneously all line conductors of the AC MAINS SUPPLY.
• Do not disconnect neutral, neutral required for system operation.If a disconnect device interrupts the neutral
conductor, it shall simultaneously interrupt all line conductors.
• When single-phase current exceeds 100A, switches of protective atmosphere should be equipped with
arc-control device.
Figure 4-6 and Figure 4-7 show the location of the UPS power cable terminals.
Table 3-6. UPS External Power Cable Terminations for the Eaton 9E 80-200 kVA
Terminal Function
Terminal
AC Input to UPS Rectifier
AC Input to Bypass
AC Output to Critical Load
DC Input from External
Battery
Customer Ground
Ground
A
B
C
NOTE
Callout letters
,
,
Maximum Size of Pressure Termination
Function
80kVA
L1
Phase A
33.62
L2
Phase B
33.62
L3
Phase C
33.62
N
Neutral
33.62
L1
Phase A
33.62
L2
Phase B
33.62
L3
Phase C
33.62
N
Neutral
33.62
L1
Phase A
33.62
L2
Phase B
33.62
L3
Phase C
33.62
N
Neutral
33.62
+
Battery (+)
53.49
Battery (-)
53.49
Ground
42.41
D
, and
map to Figure 5-5.
(mm)
100kVA
120kVA
160kVA
200kVA
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
67.43
42.41
53.49
85.01
67.43
85.01
85.01
67.43
85.01
107.22
53.49
67.43
85.01
107.22
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
UPS Installation Plan and Unpacking
Tightening Torque
Nm (lb in)
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
12(106)
85.01
85.01
12(106)
12(106)
14(124)
Screw Size and Type
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
2
. Hex
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
50.264 mm
. Hex
2
78.540 mm
. Hex
2
3-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

93e

Table of Contents