Chapter 4

UPS System Installation

4.1

Preliminary Installation Information

Installation should be performed only by qualified personnel. See installation instructions before
connecting to the supply.
Refer to the following while installing the UPS system:
• Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.
• Do not tilt the cabinets more than
• If perforated floor tiles are required for ventilation, place them in front of the UPS.
• The UPS unit is not suitable for IT or corner-earthed power distribution systems.
• Suitable for mounting on concrete or other non-combustible surfaces only
4.2
Unloading the UPS Cabinet from the Pallet
The UPS Cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet:
The UPS cabinet is heavy (see Table 3-1). If unpacking and unloading instructions are not closely followed,
the cabinet may tip and cause serious injury.
• Do not tilt cabinet more than 10° from vertical.
• Lift the cabinets only with a forklift or damage may occur.
1.
If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the installation area, or
as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
supports on the bottom of the pallet (see Figure 3-3 for the UPS cabinet centre of gravity measurements).
2.
Remove four bolts securing the front shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure 4-1). Remove the front shipping bracket. If installing the cabinet permanently, retain
the shipping bracket and securing hardware for later use.
3.
Attach the ramp to the front of the pallet (see Figure 4-2):
a.
b.
c.
4.
If the leveling feet are not fully retracted, turn the leveling feet until they are retracted.
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table 3-1 for cabinet weight).
Locate the ramp (top panel from wood container), ramp extension, and ramp brackets with M10 bolts.
Place the ramp against the front of the pallet.
Attach the ramp extension to the front of the ramp by inserting the tabs on the extension into the slots
at the bottom of the ramp.
WARNING
±
10° during installation.
WARNING
CAUTION
Eaton 9E UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual