Ups Operating Instructions; Operation; Starting The Ups - Powerware Uninterruptible Power Supply Installation And Operation Manual

Uninterruptible power supply 500 kva -- 750 kva
Table of Contents

Advertisement

UPS Operating Instructions

12.1 Operation

The following procedures provide instructions for operating the UPS system. Refer
to Chapters 10 and 11 of this manual for a description of the UPS controls and
monitor panel functions.
NOTE: 1. Before starting the UPS ensure all installation tasks are complete and a
preliminary startup has been performed by authorized service personnel.
The preliminary startup verifies all electrical interconnections to ensure the
installation was successful and the UPS operates properly.
2. The following procedures are applicable for systems with the optional
internally installed rectifier input breaker CB1 and inverter output breaker
CB3.
3. For operation of the System Bypass Module (SBM) in a Multi-module
system, refer to the applicable SBM Installation and Operation manual
referenced in the "Introduction" of this manual.

12.2 Starting the UPS

To start the UPS system, perform the following procedure:
NOTE: This procedure assumes Automode is enabled.
1.
Ensure the UPS circuit breakers are set as follows:
UPS Input Breaker (CB1)
UPS Battery Breaker or
Battery Disconnect (CB2)
UPS Output Breaker (CB3)
UPS Bypass Breaker (CB4)
Backfeed Protection Breaker (FBP) OPEN
NOTE: When feeder power is applied in steps 3 and 5, UPS circuit breakers CB1,
CB2, CB3, CB4 and FBP will charge, if not already charged.
2.
Ensure the Emergency UPM Off PUSH TO RESET pushbutton is pressed in.
3.
Close the UPS input feeder circuit breaker.
4.
Observe UPS monitor screen becoming active as an indication of logic power.
5.
Close UPS Bypass input feeder circuit breaker. Breakers CB4 and FBP will
close as soon as charged.
The critical load is immediately supplied by the bypass source, in Bypass mode, until
the inverter turns on and the UPS transfers to Normal mode. The status indicator on
the UPS Control Panel indicates the UPS is in Bypass mode.
Powerware 9315 (500 kVA- -750 kVA) Installation and Operation
164201244 REV. D 030101
12
OPEN
OPEN
OPEN
OPEN
12--1